Air Compressor User's Manual
 12  2006SSD-75 R4 (10/10) 
Dual-Compressor Module    Installation
2.6.3  Compressor Module Motor Protection
Variable Speed Compressor Module Protection
•  The two Compressors in the variable speed Compressor Module should be treated as a single 
Compressor. Both Compressors must be run at the same time to prevent oil from accumulating in 
one Compressor. Module capacity can be changed by varying the typical Compressor speed, ranging 
from 2400 to 4800 rpm.
•  If two or more Compressor Modules are used together, each module can be considered as one 
Compressor and individual modules can be turned off.
•  Each Compressor on a variable speed Compressor Module requires independent overload protection 
between the VFD and Compressor. See 2.6.1 on page 10.
Figure 10 Motor Control 
Variable
Frequency
Drive
MS2
OL2
480VAC
Variable Speed
480VAC
Fixed Speed
Drive Inhibit
MS 1 & 2 Inhibit
Compressor 2
Compressor 2Compressor 1
Compressor 1
OL1 OL2
MS1
OL1