User's Manual
Specifications
71 SOLA HD
®
S5KC
™
Table 28 Rated input voltage range (Unit: VAC)
System Configuration % UPS Load Low Limit Value High Limit Value
Dual-Inverter
Configured to 120
or 127 VAC per Phase
>100% 98 ±3.1
139.5 ±3.1
90% ~ 100% 89 ±3.1 ~ 98 ±3.1
70% ~ 90% 74 ±3.1 ~ 89 ±3.1
30% ~ 70% 60.5 ±3.1 ~ 74 ±3.1
<30% 60.5 ±3.1
Dual-Inverter
Configured to 100,
110 or 115 VAC per Phase
>100% 84 ±3.1
90% ~ 100% 80 ±3.1 ~ 84 ±3.1
70%~90% 72 ±3.1 ~ 80 ±3.1
40%~70% 60 ±3.1 ~ 72 ±3.1
<40% 60 ±3.1
Single-Inverter
Transformer-Based and
Transformer-Free
> 100% 170 ±5
280 ±5
90 ~ 100% 160 ±5 ~ 170 ±5
70 ~ 90% 140 ±5 ~ 160 ±5
50 ~ 70% 120 ±5 ~ 140 ±5
< 50% 120 ±5
Table 29 SolaHD S5KC external battery cabinet specifications
Parameters SolaHD S5KC EBC
General and Environmental
Conducted and Radiated EMC Levels IEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
Safety Standards IEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22.2 No. 107.3
Immunity Standards IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Transportation ISTA-1E
Dimensions, WxDxH 17x28x38 in. (440x712x970mm)
Unit Weight 147.7 lb. (67kg)
Shipping Weight 209.4 lb. (95kg)
Environmental
Operating Temperature 32 to 104°F (0 to 40°C)
Storage Temperature
Without battery: -4 to 140°F (-20 to 60°C)
With battery: 5 to 104°F (-15 to 40°C)
Relative Humidity 0 - 95%, non-condensing
Altitude 10,000 ft.(3000m)
Battery Module *
Lead-Acid Batteries (Per String) 12
Backup Time (Full Load), Minutes See Estimated Battery Run Times, 7.1 through 7.5
* Up to four external battery cabinets can be connected to each UPS frame and each external battery cabinet can be configured with up to
seven strings of batteries.