IntelliSlot MultiPort Card (IS-MULTIPORT)
Provides dry contact alarm information, including: On Battery, Low Battery signals for
communication to four servers for use with MultiLink software.
IntelliSlot EBC Card
This card is used for the SolaHD S5KC UPS to monitor and manage the intelligent battery modules in
external matching battery cabinets.
3.2 Dry Contact Ports
The UPS provides dry contact ports. See Figure 1 for location and Figure 46 for the pin layout.
Figure 46 Pin layout of the dry contacts
Table 14 shows the pin definition of each dry contact port.
Battery Mode Dry Contact
Pins 1 and 2: Output dry contact, normally open. The dry contact is closed when the UPS is
operating on battery. The maximum voltage and current are 24VDC and 0.3A, respectively.
Low Battery Dry Contact
Pins 3 and 4: Output dry contact, normally open. When the UPS is operating on battery, the dry
contact is closed upon battery low voltage alarm. The maximum voltage and current are 24VDC and
0.3A, respectively.
Any Mode Shut Down
Pins 5 and 6: Input dry contact, normally open. After the external dry contact is closed (shorted), the
UPS output will be shut down during any mode of operation (mains, battery, bypass).
Table 14 Pin definition of dry contact port
Position
Name Description
1 Battery Mode Output dry contact of battery mode operation
2 Battery Mode Output dry contact of battery mode operation
3 Low Battery Output dry contact of low battery operation
4 Low Battery Output dry contact of low battery operation
5 Any Mode Shut Down Input dry contact of any mode shut down
6 GND Any mode shutdown GND
7 Battery Mode Shut Down Input dry contact of battery mode shut down
8 GND Battery mode shutdown GND