User's Manual
Communication
39 SOLA HD
®
S5KC
™
3.0 COMMUNICATION
The rear panel of the SolaHD S5KC provides these communication ports:
•IntelliSlot
®
ports: 3
• Dry contact ports: 1
• REPO (Remote Emergency Power Off): 1
• Long Run Time (LRT) Battery Temperature Probe Terminals: 1
• USB port: 1
3.1 IntelliSlot Ports
The three IntelliSlot communication ports (see Figure 45) are used for installing communication
options, including the IntelliSlot Unity card, dry contact card, MultiPort and IntelliSlot EBC card.
The IntelliSlot ports and the USB port can be used at the same time.
Figure 45 IntelliSlot communication port location
IntelliSlot
Unity Cards—IS-UNITY-LIFE, IS-UNITY-DP
• IS-UNITY-LIFE: This card is standard in every SolaHD S5KC. It is used for communication
between the SolaHD S5KC UPS and Emerson’s Trellis
®
NMS and LIFE Services.
• IS-UNITY-DP: This optional card can be used instead of the standard card if communication to
two third-party platforms is required. Third-party platforms include SNMP and 485
(Modbus/Bacnet) protocols. This card would still be used for communication between the SolaHD
S5KC UPS and Emerson’s Trellis NMS and LIFE Services. All communication protocols are
active simultaneously.
IntelliSlot
®
Dry Contact Card (IS-RELAY)
Provides dry contact alarm information, including: On Battery, On Bypass, Low Battery, Summary
Alarm, UPS Fault and On UPS signals for communication to a remote monitoring system or for use
with MultiLink
®
software. This card also can accept input signals to shut down the UPS while it is in
any mode of operation.
IntelliSlot
Ports
IntelliSlot Ports
(with protective covers)