Figure 44 Battery screen
If the number displayed is not consistent with the actual installation number of external battery
cabinets:
Ensure each external battery cabinet contains two battery modules installed on the same row and
both have the locking levers in the locked position.
Ensure the IntelliSlot
®
EBC card is installed properly and the communication cables are fully
inserted in the connectors.
Determine that the DIP switch setting of each battery cabinet is correct using the following table
2.5.5 Connecting Integrated Power Output Distribution (POD)
The rear panel of the SolaHD S5KC UPS provides the capability to add integrated distribution outlets
(PODs) as an option to allow direct AC power connection of the supported equipment to the UPS.
These PODs are intended to allow the user to install and even change distribution, if necessary as
Table 13 EBC DIP switch settings
External Battery
Cabinet Number
DIP Switch Setting
12
EBC #1 UP UP
EBC #2 Down UP
EBC #3 UP Down
EBC #4 Down Down