User's Manual
Installation
31 SOLA HD
®
S5KC
™
Figure 38 Connection method
Refer to Table 7 for configuring the output cable. For standard voltages, make the connections shown
in Table 9.
Table 10 shows the maximum load capacity of the output winding of the transformer-based UPS.
Table 8 Key to Figure 38 UPS input wiring
System
Voltage
System
Nominal
Frequency
Input Terminal Block
12 PE
200 60 L1 L2 GND
208 60 L1 L2 GND
220 60 L1 L2 GND
230 60 L1 L2 GND
240 60 L1 L2 GND
200 50 L N PE
220 50 L N PE
230 50 L N PE
240 50 L N PE
Table 9 Key to Figure 38 UPS output wiring
Output
Voltage
Set Output
Voltage
by LCD
Bypass Voltage Jumper Output Voltage (Between Terminals)
208V TAP
(1-2)
240V TAP
(2-3) 1-4 3-4 2-3 1-3
200/100 200 — OK 100 100
173
(Do Not Use)
200
220/110 220 — OK 110 110
190
(Do Not Use)
220
230/115 230 — OK 115 115
199
(Do Not Use)
230
220/127 220 OK — 127 127 220
254
(Do Not Use)
240/120 240 — OK 120 120 208 240
208/120 208 OK — 120 120 208 240
If the bypass voltage jumper copper bar is connected incorrectly, the system will report a fault alarm.
When wiring to single-phase panels, connect to output terminals 1, 3, 4 and PE (GND) only.
Table 10 Maximum load capacity of the output winding
UPS Model
Maximum Output Capacity, kVA
(Between Terminals)
1-4 3-4 2-3 1-3
16-bay Transformer-based UPS 10 10 20 20
10-bay Transformer-based UPS 7.5 7.5 15 15
34GEC 2 1 1 2 3
INPUT
208V Tap
OUTPUT
12PE
240V Tap
PE
200V/208V/
220V/230V/240V
Factory-
supplied
jumper
1-3: 240V; 2-3: 208V; 1-4: 120V;
3-4: 120V (When the output voltage is
set to 240V through LCD )