Configuring the Neutral/Earth Jumper
The UPS contains an isolation transformer that generates a neutral conductor for the connected load.
The UPS is a separately derived source and contains a neutral/earth jumper. A factory-installed
neutral/earth jumper copper bar may require removal to comply with local codes and regulations.
Figure 36 Configuring the neutral/earth jumper
Connecting Cables
To connect the cable:
1. Remove the knockouts at the junction box (see Figure 37) and pull the cables through them,
leaving some slack for installation.
Figure 37 Knockouts
2. Connect the cable to the corresponding terminal of the power input and output terminals. Using a
torque wrench, tighten the screws to 12.43Nm (110 in-lb). The connections are shown in
Figure 38.
NOTE
Input and output cables must be run in separate conduit before cable connection.
Neutral/Earth Jumper
34GEC 2 1 1 2 3
INPUT
208V Tap
OUTPUT
12PE
240V Tap
PE
16-Bay SolaHD S5KC
With Transformer
12-Bay SolaHD S5KC
With Transformer