Configuring the Bypass Voltage
The UPS bypass voltage is factory-set and the copper busbar jumper has been factory-installed. If the
jumper setting does not match the input source, the bypass voltage jumper may need to be changed to
ensure the correct output voltages are provided when operating in bypass mode. Refer to Table 9 for
the proper setting location according to the AC mains voltage available and to Figures 34 and 35 for
the jumper setting location.
Figure 34 Setting bypass voltage jumper (default: 208VAC)
Figure 35 Setting bypass voltage jumper (200/220/230/240VAC)
Table 7 Input cable selection for transformer-based frames (50 Hz)
Maximum
System Rated
Load
Input Voltage - 220VAC Input Voltage - 230VAC Input Voltage - 240VAC
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
5kVA 25A 50A 24A 50A 23A 50A
10kVA 49A 63A 47A 63A 45A 63A
15kVA 73A 100A 70A 100A 67A 100A
20kVA 97A 125A 93A 125A 90A 125A
The power input and output terminals accept a maximum cable cross-sectional area of is 70mm
2
(2/0AWG); the minimum cable
cross-sectional area is 16mm
2
(6AWG). The rated torque is 12.43Nm (110 in-lb).
90°C copper wire recommended.
Jumper
34GEC 2 1 1 2 3
INPUT
208V Tap
OUTPUT
12PE
240V Tap
208VAC
PE
Jumper
34GEC 21123
INPUT
208V Tap
OUTPUT
12PE
240V Tap
240VAC
PE