User's Manual
Installation
SOLA HD
®
S5KC
™
26
2.5.1 Transformer-Free UPS Cable Connection
A junction box is factory-installed on each model of the SolaHD S5KC to ease cable connection.
Select the appropriate input cables according to Table 3 and Table 4 based on the UPS rating and
mains frequency; however, it is recommended that you size the over current protection and wiring for
the frame rating to easily allow upgrades to the UPS system.
To connect the cable:
1. Remove the knockouts at the junction box (see Figure 31) and pull the cables through them,
leaving some slack for installation.
Figure 31 Knockouts
Table 3 Input cable selection list—60Hz
Maximum
System
Rated Load
Input voltage - 200VAC Input voltage - 208VAC Input voltage - 240VAC
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
5kVA 27A 50A 26A 50A 23A 50A
10kVA 53A 63A 51A 63A 45A 63A
15kVA 80A 100A 77A 100A 67A 100A
20kVA 106A 125A 102A 125A 90A 125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm
2
(2AWG); the minimum cable
cross-sectional area is 16mm
2
(6AWG); the rated torque is 4.52Nm (40 in-lb).
Use of 90°C copper wire is recommended
Table 4 Input cable selection list—50Hz
Maximum
System
Rated Load
Input Voltage - 220VAC Input Voltage - 230VAC Input Voltage - 240VAC
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in
UPS Mode
Recommended
Input Protection
Circuit Breaker
5kVA 25A 50A 24A 50A 23A 50A
10kVA 49A 63A 47A 63A 45A 63A
15kVA 73A 100A 70A 100A 67A 100A
20kVA 97A 125A 93A 125A 90A 125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm
2
(2AWG); the minimum cable cross-
sectional area is 16mm
2
(6AWG); the rated torque is 4.52Nm (40 in-lb).
90°C copper wire recommended
NOTE
Input and output cables must be run in separate conduit before cable connection.
16-Bay SolaHD S5KC
No Transformer
10-Bay SolaHD S5KC
No Transformer