Specification Sheet
S3K Series Instruction Manual • 14Visit our Web site at www.solahd.com
10.0 Specifications
Parameter
Catalog Number
S3K700 S3K1000 S3K1600
Capacity 700 VA/480 W 1000 VA/750 W 1440 VA/1200 W
INPUT
Nominal Voltage 120 V ±25%, single phase
Frequency 50 or 60 Hz ±5% (auto-sensing)
OUTPUT
Voltage (on battery) Pure sine wave output at nominal ±5%
Frequency (on battery) 50 or 60 Hz ±0.5%
Voltage Regulation
(AVR)
AVR automatically increases output voltage 15% above input voltage if
-9% to -25% of nominal is detected. AVR decreases output voltage 15%
below input voltage if +9% to +25% of nominal is detected.
PROTECTION & FILTERING
Spike Protection 320 J, 2 ms
Unit Input Fuse for overload & short circuit protection
EMI/RFI Filter 10 dB at 0.15 MHz; 50 dB at 30 MHz
Overload Protection
UPS automatically shuts down if overload exceeds
100% of nominal at 20 s and 125% at 2 s
Transfer Time 2–4 ms, including detection time
Short Circuit UPS output cuts off immediately or input fuse protection
ENVIRONMENT
Operating Temperature 0°C to +40°C
Humidity 0 to 95%, non-condensing
Maximum Elevation 10,000 ft. (3,000 m)
Audible Noise
<40 dBA
(1 m from surface)
<45 dBA
(1 m from surface)
PHYSICAL
Dimensions (W x D x H),
inches [mm]
5.5 x 17.2 x 8.27
[140 x 436 x 210]
6.7 x 17.7 x 8.9
[170 x 450 x 226]
Net Weight, lb. [kg] 31.9 [14.5] 34.8 [15.8] 66.0 [30.0]
Shipping Weight, lb. [kg] 34.1 [15.5] 37.0 [16.8] 70.4 [32.0]
Input Inlet IEC 320 power inlet to 5-15P plug line cord Attached cord to 5-15P
Output Receptacles (4) NEMA 5-15R (6) NEMA 5-15R
BATTERY
Type Hot swappable, sealed, maintenance-free, lead acid
Typical Recharge Time 4 hours (to 90% of full capacity)
Protection Automatic self-test & discharge protection. Replace battery indicator.
Backup Time 10–30 min. (depending on the load)