Data Sheet

Bulletin 71.1:S200
5
Table 1. Available Constructions







S202

















Light diaphragm plate X X X X X X X
Heavy diaphragm plate X X X X X X X X X X X
Either light or heavy diaphragm plate
depending on outlet pressure range
X X X X X
Internal registration X X X X X X X X X X X X X X X X
External registration - O-ring stem seal
and downstream control line connection
X X X X X X X
Internal relief - Full X X X X X
Internal relief - Token X X X X X X
True-Monitor
X X X
Low outlet pressure shutoff X X X X
Type VSX-2 X X X X X X X X

Cast Iron X X X X X X X X X X X X X X X
Ductile Iron X X X X X X X X X X X X X X X X
Steel X X X X X X X X
Table 2. Body Sizes and End Connection Styles
 
    
1-1/4
1-1/2
1-1/2 x 2
32
40
40 x 50
NPT, BSP
NPT, BSP
- - - -
- - - -
NPT, BSP
NPT, BSP
- - - -
NPT, BSP
- - - -
2 50 NPT; BSP; or CL125 FF
(1)
NPT; BSP; CL125 FF or
CL250 RF anged; or
PN 10-16 anged
NPT; BSP; CL150 RF;
or PN 10-16 anged
1. This ange is available with a face-to-face of 7.5 inches / 191 mm or 10 inches / 254 mm.
Table 3. Outlet Pressure Ranges






 
S201, S202, S203
(1)
, S208, S209,
S201P, S202P, S203P,
S208P, and S209P
- - - -
1
2
3
4
2 to 4.5 inches w.c. / 5 to 11 mbar
(2)(3)
3.5 to 6.5 inches w.c. / 9 to 16 mbar
5 to 9 inches w.c. / 12 to 22 mbar
8.5 to 18 inches w.c. / 21 to 45 mbar
14 to 30 inches w.c. / 35 to 75 mbar
1D892527022
1D892627022
1D892727012
1D893227032
1D893327032
Brown
Red
Black
Gray
Dark Green
S204 and S206
- - - -
- - - -
- - - -
- - - -
- - - -
3.5 to 5 inches w.c. / 9 to 12 mbar
(2)
5 to 7 inches w.c. / 12 to 17 mbar
6.5 to 9.5 inches w.c. / 16 to 23 mbar
8.5 to 18 inches w.c. / 21 to 45 mbar
14 to 30 inches w.c. / 35 to 75 mbar
1D892527022
1D892627022
1D892727012
1D893227032
1D893327032
Brown
Red
Black
Gray
Dark Green
S201H, S202H, S203H
(1)
, S208H, S209H,
S201P
(4)
, S202P
(4)
, S203P
(4)
,
S204H, S206H, S208P
(4)
, and S209P
(4)
5
6
7
1 to 2 psig / 0.07 to 0.14 bar
1.5 to 3.25 psig / 0.10 to 0.22 bar
2 to 5 psig / 0.14 to 0.34 bar
(5)
1H975827032
1H975927032
1P615427142
Dark Blue
Orange
Yellow
S201K, S201PK,
S208K, and S208PK
8
9
2 to 5.5 psig / 0.14 to 0.38 bar
4 to 10 psig / 0.28 to 0.69 bar
0Y066427022
1H802427032
Green Stripe
Unpainted
S204H and S206H
- - - -
- - - -
1 to 2 psig / 0.07 to 0.14 bar
1.5 to 3.25 psig / 0.10 to 0.22 bar
1H975827032
1H975927032
Dark Blue
Orange
1. Types S203 and S203H outlet pressure ranges are a function of the monitor construction / monitor spring and the number of spring seats used. See Table 5 for more information.
2. With regulator installed so control spring is on top of diaphragm. If installed so control spring is on bottom, lower end of outlet pressure range can be reduced by 1 inch w.c. / 2 mbar for
regulator with light diaphragm plate or 2 inches w.c. / 5 mbar for regulator with heavy diaphragm plate.
3. Not available with Types S208 and S209.
4. Types S201P, S202P, S203P, S208P, and S209P require heavy diaphragm plate for outlet pressures over 1 psig / 0.07 bar.
5. Not available for Types S203P, S204H, and S206H.