Data Sheet

Bulletin 71.1:S200
13



















     
Overpressure
Shutoff
Internal or
External
1, 2 12 to 25 30 to 62 T14162T0012 Black 3.15 80.0 0.067 1.70
1, 2, 3, 4 20 to 52 50 to 129 T14163T0012 Brown 3.15 80.0 0.080 2.03
3, 4, 5, 6 1.4 to 3.9 psig 0.10 to 0.27 bar T14164T0012 Red 3.15 80.0 0.091 2.31
5, 6, 7, 8, 9 3.8 to 8.7 psig 0.26 to 0.60 bar T14165T0012 Orange 3.15 80.0 0.120 3.05
9 5.8 to 16 psig 0.40 to 1.1 bar T14166T0012 Pink 3.15 80.0 0.138 3.51
Underpressure
Shutoff
External
2, 3 2 to 12 5 to 30 T14168T0012 White 3.15 80.0 0.043 1.09
3, 4, 5, 6 4 to 30 10 to 75 T14169T0012 Blue 3.15 80.0 0.055 1.40
5, 6, 7, 8 10 inches w.c. to 2.3 psig 25 mbar to 0.16 bar T14170T0012 Silver 3.15 80.0 0.067 1.70
7, 8, 9 1.5 to 10.8 psig 0.10 to 0.75 bar T14171T0012 Olive 3.15 80.0 0.125 3.18
Internal
2, 3, 4
(3)
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
5, 6
(4)
50% of regulator setpoint
to 30 inches w.c.
50% of regulator setpoint
to 75 mbar
T14169T0012 Blue 3.15 80.0 0.055 1.40
5, 6, 7, 8
(4)
50% of regulator setpoint
to 2.3 psig
50% of regulator
setpoint to 0.16 bar
T14170T0012 Silver 3.15 80.0 0.067 1.70
7, 8
(4)
50% of regulator setpoint
to 10.8 psig
50% of regulator
setpoint to 0.75 bar
T14171T0012 Olive 3.15 80.0 0.125 3.18
9
(4)
70% of regulator setpoint
to 10.8 psig
70% of regulator
setpoint to 0.75 bar
T14171T0012 Olive 3.15 80.0 0.125 3.18
1. See Table 3 for main valve spring number.
2. Other spring combinations are available, please contact your local Sales Of ce for additional information. Trip pressure that are 2 or 3 psig/ 0.14 to 0.21 bar over set pressure may result in
internal parts damage.
3. Regulator main valve spring numbers 2, 3, and 4 cannot be used with an internally registered Type VSX-2 to provide underpressure shutoff under  owing conditions. If protection
against loss of inlet pressure is the only required function for the Type VSX-2 then an internally registered Type VSX-2 may be used with the same minimum trip pressure as an
externally registered Type VSX-2.
4. 50% of regulator setpoint is the minimum allowable underpressure shutoff setting for an internally registered Type VSX-2 used with main valve spring numbers 5, 6, 7, and 8. 70% of
regulator setpoint is the minimum allowable underpressure shutoff setting for an internally registered Type VSX-2 used with main valve spring number 9. If the protection against loss of inlet
pressure is the required function for the Type VSX-2 then an internally registered Type VSX-2 may be used with the same minimum trip pressure as an externally registered Type VSX-2.
Table 6. Type VSX-2 High and Low Trip Pressure Ranges
Figure 11. Type S208 Regulator with Type VSX-2 Slam-Shut Device (right) and Type S209 Regulator with Slam-Shut Device and
Internal Token Relief (left)





