7.0 Troubleshooting
UPSisofforOn/Off/Testbuttonwas
notpushedlongenough
PresstheOn/Off/Testbuttonformore
than2seconds
Batteryvoltageislessthan10V
(20VforS1K1500)
RechargetheUPSforatleast4
hours.Ifitstilldoesnotstart,check
theinputfuse.
Otherfailure CallSolaHDTechnicalSupport
Loadlessthan20WinBackupMode Normalcondition
Powercordisloose Pluginthepowercord
Inputacpowerisnotavailable Checkfuses/breakers
Otherfailure,PCB,etc. CallSolaHDTechnicalSupport
Linevoltagetoohigh,toolow,or
blackout
Normalcondition
Batteryisnotfullycharged
RechargetheUPSforatleast4
hours
Otherfailure CallSolaHDTechnicalSupport
Overloadcondition Removethenon-criticalloads
Batteryfailure CallSolaHDTechnicalSupport
8.0 Storage
Beforestoring,chargetheUPSforatleast4hours.
StoretheUPScoveredanduprightinacool,drylocationwithitsbatteryfully
charged.Removeanyaccessoriesfromtheaccessoryslotanddisconnectany
cablesconnectedtotheRemotePorttoavoidunnecessarydrainingofthebattery.
Duringextendedstorageinenvironmentswheretheambienttemperatureis
-15°Cto+30°C(+5°Fto+86°F),chargetheUPSbatteryevery6months.
Duringextendedstorageinenvironmentswheretheambienttemperatureis
+30°Cto+45°C(+86°Fto+113°F),chargetheUPSbatteryevery3months.