Uninterruptible Power Systems S1K Series Instruction Manual
Contents 1.0 Important Safety Instructions....................................................................................................... 4 1.1 Safety Precautions...............................................................................................................................................4 1.2 Conditions of Use.................................................................................................................................................5 2.0 System Description....
1.0 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Congratulations on your choice of the SolaHD S1K Series Uninterruptible Power System (UPS). This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS. Please read this manual thoroughly, including all safety, installation, and operating instructions before attempting to install or operate this UPS.
• Do not place the UPS under direct sunlight or close to heat emitting sources. • To allow proper ventilation of the UPS, do not block or cover the top and/or bottom sides of the unit. • Do not place the UPS power cord in any area where it may get damaged by heavy objects. • Follow all warnings and instructions marked on the UPS. Do not attempt to service the UPS, as it has no user-serviceable parts inside • Do not dispose of batteries in a fire; they may explode. • Do not open or damage the battery.
2.0 System Description 2.
2.2 Front & Rear Panel Descriptions For Models S1K650, S1K850, and S1K1200: 1. Battery Fault indicator (red LED): The red LED illuminates when the UPS battery is no longer useful. ! CAUTION: Do not attempt to open the UPS or replace the battery; call SolaHD Technical Support at (800) 377-4384. 2. Backup indicator (yellow LED): The yellow LED illuminates when the UPS is supplying battery power to the loads. 3.
3.0 Preinstallation 3.1 Inspection Inspect the UPS upon receipt. Damage that may have occurred in transit is not covered under the warranty. If shipping damage is present, please contact your local carrier and SolaHD distributor immediately. NOTE: The packaging material is recyclable. Please reuse or dispose of it in a responsible manner. 3.2 What’s Included • CD with UPSMON monitoring software • Instruction Manual • (1) DB-9 RS-232 cable • (1) RJ-45 cable 3.
5.0 Operating Instructions 5.1 UPS Protected Output Outlets The output outlets will provide protection from surges and power failures. Plug your computer, monitor, and other “data critical” devices into these outlets. 5.2 Surge Protected Outlet Only The surge protected outlet can offer protection against surges and transients typically caused by lightning or disruptive loads in the building. In the event of utility power failure, this outlet will not provide backup power to the load.
6.0 Alarms 6.1 Backup (slow beeping) For Models S1K650, S1K850, and S1K1200: When in Backup Mode, the yellow LED illuminates and the UPS sounds an audible alarm. The alarm stops when the UPS returns to Line Normal operation. For Models S1K320, S1K520, and S1K1500: When in Backup Mode, the green LED flashes slowly and the UPS sounds an audible alarm. The alarm stops when the UPS returns to Line Normal operation. 6.
7.0 Troubleshooting Table 1: Troubleshooting Problem UPS is not on; green LED will not illuminate UPS is always in Backup Mode Backup time is too short Cause Solution UPS is off or On/Off/Test button was not pushed long enough Press the On/Off/Test button for more than 2 seconds Battery voltage is less than 10 V (20 V for S1K1500) Recharge the UPS for at least 4 hours. If it still does not start, check the input fuse.
9.0 Software & Interface 9.1 Power Monitoring Software UPSMON software (or other power monitoring software) utilizes a standard RS-232 interface to perform monitoring functions and an orderly shutdown of the protected equipment in the event of power failure. UPSMON displays all the diagnostic symptoms on the monitor, including voltage, frequency, and battery levels. UPSMON is available for Windows applications and other OS compatible solutions. Please contact SolaHD Technical Support for more information.
10.0 Specifications Table 3: Technical Specifications Model Parameters Capacity, VA/W S1K320 S1K520 S1K650 S1K850 S1K1200 S1K1500 320/240 520/360 650/390 850/600 1200/720 1500/900 input Voltage (Single phase) 115 V ± 25% 115 V ± 20% Frequency 115 V ± 25% 50 or 60 Hz ± 10% (auto sensing) Output Step sine wave at 115 V Voltage (on battery) ± 10% ± 5% 50 or 60 Hz Frequency (on battery) ± 0.
Table 4: Typical Battery Backup Times Load Model S1K320 S1K520 S1K650 S1K850 S1K1200 S1K1500 Backup Times (hr:min:s) 10% 02:18:00 01:35:00 01:36:00 00:54:00 00:45:00 01:16:15 20% 01:03:30 00:42:00 00:58:00 00:30:00 00:27:00 00:28:00 30% 00:35:45 00:21:00 00:36:00 00:21:00 00:19:00 00:12:30 40% 00:22:30 00:12:30 00:20:00 00:17:00 00:14:00 00:07:30 50% 00:15:00 00:08:00 00:14:00 00:11:00 00:08:00 00:04:30 60% 00:11:45 00:06:00 00:10:00 00:08:00 00:05:00 00:04:30
www.solahd.com (800) 377-4384 • (847) 268-6651 solahd.technicalservices@emerson.