Specifications
748414-A
August 1999
14
Heated Flame Ionization Detector Analyzer Module
Rosemount Analytical NGA 2000
2
INSTALLATION
2.6 INSTALLATION CONSIDERATIONS CHECKLIST
Verify the following:
• The Analyzer’s location should be:
Clean
A well ventilated area
weatherproofed
Non-hazardous
Vibration-free
Have stable ambient temperature
• The gas cylinders should be equipped with a clean, hydrocarbon free two stage
regulator and shut off valve.
• All external tubing, regulators, valves, pumps, fittings, etc. are clean.
• The correct fuel type is being used.
• The THC content of the supply gases are compatible with the analysis range.
• The calibration background gases are similar to the sample.
• The purge air out, burner exhaust, and bypass are vented to atmospheric pressure. The
pressure should be constant.
• The burner exhaust tube must be slanted down a minimum of 6 degrees from horizontal.
• The bypass line connection must be slanted down a minimum of 6 degrees from
horizontal for drainage of water condensation.
• If required, thermal insulation around the bypass fitting to prevent condensation in the
bypass restrictor.
• If required, thermal insulation for the sample inlet connection to minimize the cold spot.
• The heated line is at the correct temperature.
• The sample, zero, and span gases are at the correct temperature.
• The heated line to have over temperature protection.
• The sample, bypass, and burner exhaust tubing material must handle high temperature
and have thermal insulation to protect from burns.
• The purge air out tubing to be 3/8 inch and less than 4 feet in length.