00825-0100-4774_RevFA.fm Page 1 Friday, June 6, 2014 2:21 PM Quick Start Guide 00825-0100-4774, Rev FA June 2014 Rosemount® 3051 Pressure Transmitter Rosemount 3051CF Series Flowmeter Transmitter with FOUNDATION™ fieldbus protocol Note Before installing the transmitter, confirm the correct device driver is loaded on the host systems. See “System readiness” on page 3.
00825-0100-4774_RevFA.fm Page 2 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide NOTICE This installation guide provides basic guidelines for Rosemount 3051 transmitters. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, Explosion-Proof, Flame-Proof, or intrinsically safe (I.S.) installations. Refer to the 3051 reference manual (document number 00809-0100-4774) for more instruction. This manual is also available electronically on www.
00825-0100-4774_RevFA.fm Page 3 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 System readiness Confirm correct device driver Verify the correct device driver (DD/DTM™) is loaded on your systems to ensure proper communications. Download the correct device driver at your host vendor download site, www.emersonprocess.com or www.fieldbus.org.
00825-0100-4774_RevFA.fm Page 4 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide Figure 1. Installation Flowchart Start Locate device 1. Transmitter installation 6. Configuration 2. Commissioning tag 7. Zero trim the transmitter 3. Housing rotation Done 4. Set switches and software write lock 5.
00825-0100-4774_RevFA.fm Page 5 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 Transmitter installation Step 1: Mount the transmitter Liquid applications Coplanar In-Line Coplanar In-Line Coplanar In-Line 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Gas applications 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Steam applications 1.
00825-0100-4774_RevFA.fm Page 6 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide Figure 2. Panel and Pipe Mounting Panel mount(1) Pipe mount Coplanar flange Traditional flange Rosemount 3051T 1. 1. 5/16 x 1 1/2 Panel Bolts are customer supplied. Bolting considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow the assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters.
00825-0100-4774_RevFA.fm Page 7 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 Figure 3. Common Transmitter Assemblies A D C 4 x 2.25-in. (57 mm) 4 x 1.75-in. (44 mm) B 4 x 1.75-in. (44 mm) 4 x 1.50-in. (38 mm) 4 x 2.88-in. (73 mm) 4 x 1.75-in. (44 mm) A. Transmitter with Coplanar Flange B. Transmitter with Coplanar Flange and Optional Flange Adapters C. Transmitter with Traditional Flange and Optional Flange Adapters D.
00825-0100-4774_RevFA.fm Page 8 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide Table 2. Torque Values for the Flange and Flange Adapter Bolts Bolt material Head markings B7M Carbon Steel (CS) 316 B8M 316 R STM 316 Initial torque Final torque 300 in.-lbs. 650 in.-lbs. 150 in.-lbs. 300 in.-lbs. 316 Stainless Steel (SST) SW 316 O-rings with flange adapters Failure to install proper flange adapter O-rings may cause process leaks, which can result in death or serious injury.
00825-0100-4774_RevFA.fm Page 9 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the o-rings, re-torque the flange bolts and alignment screws after installation to compensate for seating of the PTFE o-ring.
00825-0100-4774_RevFA.fm Page 10 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide Figure 6. Commissioning Tag Commissioning Tag Commissioning Tag DEVICE ID: DEVICE ID: 0011513051010001440-121698091725 001151AC00010001440-121698091725 DEVICE REVISION: 7.2 DEVICE REVISION: 8.1 PHYSICAL DEVICE TAG PHYSICAL DEVICE TAG A DEVICE ID: 0011513051010001440-121698091725 DEVICE ID: 001151AC00010001440-121698091725 Device Barcode Device Barcode DEVICE REVISION: 7.2 DEVICE REVISION: 8.
00825-0100-4774_RevFA.fm Page 11 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 Step 4: Set the switches Set Simulate and Security switch configuration before installation as shown in Figure 8. The simulate switch enables or disables simulated alerts and simulated AI Block status and values. The default simulate switch position is enabled. The Security switch allows (unlocked symbol) or prevents (locked symbol) any configuration of the transmitter.
00825-0100-4774_RevFA.fm Page 12 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide Step 5: Wire, ground, and power up Use of copper wire of sufficient size to ensure that the voltage across the transmitter power terminals does not drop below 9 vdc. Power supply voltage can be variable, especially under abnormal conditions such as when operating on battery backup. A minimum of 12 vdc under normal operating conditions is recommended. Shielded twisted pair Type A cable is recommended. 1.
00825-0100-4774_RevFA.fm Page 13 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 a. Trim the cable shield as short as practical and insulate from touching the transmitter housing. Note Do NOT ground the cable shield at the transmitter; if the cable shield touches the transmitter housing, it can create ground loops and interfere with communications. b. Continuously connect the cable shields to the power supply ground. c.
00825-0100-4774_RevFA.fm Page 14 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide When the user exits the “Locate Device” method, the device LCD display automatically returns to normal operation. Note Some hosts do not support “Locate Device” in the DD. Step 6: Configure Each FOUNDATION fieldbus host or configuration tool has a different way of displaying and performing configurations.
00825-0100-4774_RevFA.fm Page 15 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 Figure 11.
00825-0100-4774_RevFA.fm Page 16 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 a. Navigation: from the overview screen, select “Device Information” and then select the “Security and Simulation” tab. b. Perform “Write Lock Setup” to disable Software Write Lock. Note Place the control loop in “Manual” mode before beginning Analog Input Block configuration. AI block configuration 1. To use guided setup: a. Navigate to Configure, then Guided Setup. b. Select “AI Block Unit Setup”.
00825-0100-4774_RevFA.fm Page 17 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 Note If the L_TYPE selected in Step 3 is “Direct”, Step 4, Step 5 and Step 6 are not needed. If the L_TYPE selected is “Indirect”, Step 6 is not needed. If guided setup is used any unneeded steps will automatically be skipped. 3. To select the Signal Conditioning “L_TYPE” from the drop down menu: a. Select L_TYPE: “Direct” for pressure measurements using the device default units. b.
00825-0100-4774_RevFA.fm Page 18 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 8. Configure optional LCD display (if installed). a. To use guided setup: Navigate to Configure, Guided Setup, and select “Local Display Setup”. Note Guided setup will automatically go through each step in the proper order. Check the box next to each parameter to be displayed to a maximum of four parameters. The LCD display will continuously scroll through the selected parameters. b.
00825-0100-4774_RevFA.fm Page 19 Friday, June 6, 2014 2:21 PM Quick Start Guide June 2014 AI block configuration parameters Use the Pressure, DP Flow, and DP Level examples for guides. Parameters Enter data Channel 1=Pressure, 2=Sensor Temp, 12=SPM mean, 13=SPM standard deviation L-Type Direct, Indirect, or Square Root XD_Scale Scale and Engineering Units Note Select only the units that are supported by the device.
00825-0100-4774_RevFA.fm Page 20 Friday, June 6, 2014 2:21 PM June 2014 Quick Start Guide DP Level example Parameters Enter data Channel 1 L_Type Indirect XD_Scale 0 - 300 inH20 @ 68 °F Note Select only the units that are supported by the device. Out_Scale 0-25 ft. Display pressure on the LCD display Select the 'pressure' check box on the display configuration screen.
March 2014 Quick Start Guide 3051 Product Certifications Rev 1.0 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.
March 2014 Quick Start Guide Markings: Explosionproof for Class I, Division 1, Groups B, C and D; Suitable for Class I, Zone 1, Group IIB+H2, T5; Dust-Ignitionproof Class II, Division 1, Groups E, F, G; Class III Division 1; Intrinsically Safe Class I, Division 1 Groups A, B, C, D when connected in accordance with Rosemount drawing 03031-1024, Temperature Code T3C; Suitable for Class I, Zone 0; Class I Division 2 Groups A, B, C and D, T5; Suitable for Class I Zone 2, Group IIC; Type 4X; Factory Sealed; Si
March 2014 Quick Start Guide Special Conditions for Safe Use (X): 1. The apparatus is not capable of withstanding the 500 V insulation test required by EN60079-11. This must be taken into account when installing the apparatus. 2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however care should be taken to protect it from impact or abrasion if located in Zone 0. 3. Some variants of the equipment have reduced markings on the nameplate.
March 2014 Quick Start Guide 2. 3. 4. I7 For information on the dimensions of the flameproof joints the manufacturer shall be contacted. The capacitance of the wrap around label, being 1.6 nF, exceeds the limit in Table 9 of EN60079-0. The user shall determine suitability for the specific application. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking. IECEx Intrinsic Safety Certificate: IECEx BAS 09.
March 2014 Quick Start Guide Brazil E2 INMETRO Flameproof Certificate: UL-BR 13.0643X Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-1:2009 + Errata 1:2011, ABNT NBR IEC60079-26:2008 + Errata 1:2008 Markings: Ex d IIC T6/T5 Ga/Gb, T6(-50°C ≤ Ta ≤ +65°C), T5(-50°C ≤ Ta ≤ +80°C) Special Conditions for Safe Use (X): 1. This device contains a thin wall diaphragm.
Quick Start Guide March 2014 China E3 China Flameproof Certificate: GYJ14.1041X; GYJ10.1313X [Flowmeters] Standards: GB3836.1-2000, GB3836.2-2010, GB12476-2000 Markings: Ex d IIC T6/T5, T6(-50°C ≤ Ta ≤ +65°C), T5(-50°C ≤ Ta ≤ +80°C) Special Conditions of Use (X): 1. The relation between ambient temperature arrange and temperature class is as follows: Ta Temperature Class -50°C~+80°C T5 -50°C~+65°C T6 When used in a combustible dust environment, the maximum ambient temperature is 80°C. 2.
March 2014 4. 5. 6. 7. 8. Quick Start Guide Power Pi 0.9 W 1.3 W 5.32 W Capacitance Ci 0.012 µF 0 µF <5 nF Inductance Li 0 mH 0mH <10 µH Note 1: FISCO parameters apply to both Group IIC and IIB. Note 2: [For Flowmeters] When 644 temperature transmitter is used, the 644 temperature transmitter should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres.
Quick Start Guide March 2014 GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)” GB3836.
00825-0100-4774_RevFA.
00825-0100-4774_RevFA.
00825-0100-4774_RevFA.
00825-0100-4774_RevFA.
00825-0100-4774_RevFA.
00825-0100-4774_RevFA.fm Page 26 Friday, June 6, 2014 2:21 PM ?00825-0100-4774? Quick Start Guide 00825-0100-4774, Rev FA June 2014 Device revision Host (1) 8 Device driver (DD)(2) Obtain at All DD4: DD Rev 1 www.fieldbus.org All DD5: DD Rev 1 www.fieldbus.org Emerson AMS V 10.5 or higher: DD Rev 2 www.emersonprocess.com Emerson AMS V 8 to 10.5: DD Rev 1 www.emersonprocess.com Emerson 375 / 475: DD Rev 2 Easy Upgrade Utility Device driver (DTM) www.emersonprocess.