Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Hygienic Pressure Transmitter for Life Sciences Applications 74 www.rosemount.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Rosemount 4500 Hygienic Pressure Transmitter NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product. Rosemount Inc. has two toll-free assistance numbers: Customer Central Technical support, quoting, and order-related questions.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Table of Contents SECTION 1 Introduction Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 SECTION 2 Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Safety Messages . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 4500 00809-0100-4027, Rev AA December 2005 Scaled Variable Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 Re-mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17 Sensor Temperature Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18 Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18 Transmitter Test . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4027, Rev AA December 2005 Section 1 Rosemount 4500 Introduction Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1 Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2 USING THIS MANUAL www.rosemount.com The sections in this manual provides information on installing, operating, and maintaining the Rosemount 4500 pressure transmitter.
Reference Manual Rosemount 4500 SERVICE SUPPORT 00809-0100-4027, Rev AA December 2005 To expedite the return process outside of the United States, contact the nearest Rosemount representative. Within the United States, call the Rosemount National Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
Reference Manual 00809-0100-4027, Rev AA December 2005 Section 2 Rosemount 4500 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4 Installing the LCD Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-8 OVERVIEW The information in this section covers installation considerations.
Reference Manual Rosemount 4500 00809-0100-4027, Rev AA December 2005 CONSIDERATIONS General Measurement accuracy depends upon proper installation of the transmitter. Mount the transmitter close to the process and use a minimum of piping to achieve best accuracy. Also, consider the need for easy access, personnel safety, practical field calibration, and a suitable transmitter environment. Install the transmitter to minimize vibration, shock, and temperature fluctuation.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Figure 2-2.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 INSTALLATION PROCEDURES For dimensional drawing information refer to Appendix A: Reference Data. Electronics Housing Provide 0.75 inches (19 mm) of clearance for units without an LCD display. Three inches of clearance is required for cover removal if a meter is installed. Cover Installation Always ensure a proper seal by installing the electronics housing cover so the o-ring is engaged. Use Rosemount O-rings.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 NOTE Sensor burst pressure limits may be less than clamp pressure limits. NOTE Most transmitters are calibrated in the vertical position. Mounting the transmitter in any other position will shift the zero point to the equivalent amount of liquid head caused by the varied mounting position. To reset zero point, refer to “Sensor Trim” on page 4-5.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 HART Communicator Fast Keys 1, 3, 4, 5 Usage Note The HART Communicator can be used to configure the security on and off. Otherwise, if the transmitter contains the D1 option, the switch will override any software configuration. AMS Right click on the device and select “Device Configuration”, then “Config Write Protect” from the menu. 1. Enter write protect setting, click Next. 2. Click Next to acknowledge setting has changed.
Reference Manual 00809-0100-4027, Rev AA December 2005 Connect Wiring and Power Up Rosemount 4500 Wiring for HART Protocol NOTE Use shielded twisted pairs to yield best results. To ensure proper communication, use 24 AWG or larger wire, and do not exceed 5000 feet (1 500 meters). Figure 2-5. HART Terminal Blocks Y IT R CU AL +LOOP SE AR M -LOOP SPAN ZERO -LOOP 4500_25_AA.EPS +LOOP To make connections, perform the following procedure: 1. Remove the housing cover. 2.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Grounding Transmitter Case Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case include: • INSTALLING THE LCD METER Internal Ground Connection: The Internal Ground Connection screw is inside the electronics housing.
Reference Manual 00809-0100-4027, Rev AA December 2005 Section 3 Rosemount 4500 Configuration Commissioning on the bench With HART . . . . . . . . . . . . page 3-2 Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . page 3-6 Check Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-7 Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-8 LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Rosemount 4500 COMMISSIONING ON THE BENCH WITH HART 00809-0100-4027, Rev AA December 2005 Commissioning consists of testing the transmitter and verifying transmitter configuration data. 4500 transmitters can be commissioned either before or after installation. Commissioning the transmitter on the bench before installation using a 375 Field Communicator or AMS ensures that all transmitter components are in working order.
Reference Manual 00809-0100-4027, Rev AA December 2005 Wiring Diagrams Rosemount 4500 Bench Hook-up Connect the bench equipment as shown in Figure 3-1, and turn on the HART Communicator by pressing the ON/OFF key or log into AMS. The HART Communicator or AMS will search for a HART-compatible device and indicate when the connection is made. If the HART Communicator or AMS fail to connect, it indicates that no device was found. If this occurs, refer to Section 5: Troubleshooting. Figure 3-1.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 HART COMMUNICATOR Menu Tree 1. PROCESS VARIABLES 2. DIAG/SERVICE 1. 2. 3. 4. 5. 6. Pres Percent Range Analog Output (AO) Snsr temp SV PV is 1. TEST DEVICE 2. Loop Test 3. CALIBRATION 3. BASIC SETUP 1. Tag 2. Unit 3. RANGE VALUES 4. 5. 6. 7. 1. Self test 2. Status 1. Keypad Input 2. Apply Values 1. RERANGE 1. Digital-to-Analog Trim 2. Scaled D/A Trim 2. ANALOG OUTPUT TRIM 3. SENSOR TRIM 4. Recall fact trim 1. 2. 3. 4. 5. 6. 7.
Reference Manual 00809-0100-4027, Rev AA December 2005 Fast Key Sequence Rosemount 4500 The following menu indicates fast key sequences for common functions. For full 375 Field Communicator menu tree see www.rosemount.com.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Review Configuration Data Fast Keys 1, 5 NOTE Information and procedures in this section that make use of HART Communicator fast key sequences and AMS assume that the transmitter and communication equipment are connected, powered, and operating correctly. HART Communicator Before placing the transmitter into operation, review the transmitter configuration data below which was set by the factory.
Reference Manual 00809-0100-4027, Rev AA December 2005 CHECK OUTPUT Before performing other transmitter on-line operations, review the digital output parameters to ensure that the transmitter is operating properly and is configured to the appropriate process variables. Process Variables Fast Keys Rosemount 4500 1, 1 The process variables for the 4500 provide transmitter output, and are continuously updated.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 BASIC SETUP Set Process Variable Units Fast Keys 1, 3, 2 The PV Unit command sets the process variable units to allow you to monitor your process using the appropriate units of measure. HART Communicator Enter the fast key sequence for “Set Process Variable Units.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Rerange with a HART Communicator Only Fast Keys 1, 2, 3, 1, 1 The easiest way to rerange is to use the HART Communicator only. This method changes the values of the analog 4 and 20 mA points independently without a pressure input. From the HOME screen, enter the fast key sequence for “Rerange with a Communicator Only.” 1. At “Keypad Input” select 1 and use the keypad to enter lower range value. 2.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Rerange with AMS only Right click on the device and select “Configuration Properties” from the menu. In the Basic Setup tab, locate the Analog Output box and perform the following procedure: 1. Enter the lower range value (LRV) and the upper range value (URV) in the fields provided. Click Apply. 2. An “Apply Parameter Modification” screen appears, enter desired information and click OK. 3.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 LCD Display Configuration Fast Keys 1, 3, 7 The Meter Options command customizes the LCD display. The LCD display display will alternate between the items selected. Configure the meter to display the following information to suit your application needs: • Engineering Units • Percent of Range • Scaled Variable • Temperature AMS Right click on the device and select “Configuration Properties” from the menu. 1.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Table 3-1. Rosemount (Standard) Alarm and Saturation Values Table 3-2. NAMUR-Compliant Alarm and Saturation Values Table 3-3. Custom Alarm and Saturation Values Level 4–20 mA Saturation 4–20 mA Alarm Low High 3.9 mA 20.8 mA ≤ 3.75 mA ≥ 21.75 mA Level 4–20 mA Saturation 4–20 mA Alarm Low High 3.8 mA 20.5 mA ≤ 3.6 mA ≥ 22.5 mA Level 4–20 mA Saturation 4–20 mA Alarm Low High 3.7 mA — 3.9 mA 20.1 mA — 21.5 mA 3.6 mA — 3.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Right click on the device, select “Device Configuration”, then select “Alarm/Saturation Levels,” then “Alarm Levels” from the menu. 1. Click Next after setting the control loop to manual. 2. Click Next after acknowledging the current alarm levels. 3. Select the desired alarm settings: NAMUR, Rosemount, Other 4. If “Other” is selected, enter desired “HI Value” and “LO Value” custom values. 5.
Reference Manual Rosemount 4500 00809-0100-4027, Rev AA December 2005 Alarm Level Verification If the transmitter electronics board, Transmitter, or LCD display is repaired or replaced, verify the transmitter alarm level before returning the transmitter to service. This feature is also useful in testing the reaction of the control system to a transmitter in an alarm state.
Reference Manual 00809-0100-4027, Rev AA December 2005 Scaled Variable Configuration Fast Keys Rosemount 4500 The scaled variable configuration allows the user to create a relationship/conversion between the pressure reading and custom units. 1, 4, 3, 4, 7 The scaled variable configuration defines the following items: • Scaled variable units - Custom units to be displayed. • Scaled data options - Defines the transfer function for the application a. Linear b.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 HART Communicator To configure the scaled variable with a HART Communicator, perform the following procedure: 1. From the HOME screen follow the fast key sequence for “Scaled Variable Configuration.” 2. Select OK after the control loop is set to manual. 3. Enter the scaled variable units. a. Units can be up to six characters long and include A — Z, 0 — 9, -, /,%, and *. b.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Right click on the device and select “Device Configuration” then select “SV Config” from the menu. 1. Click Next after setting the control loop to manual. 2. Enter desired scaled variable units in “Enter SV units” box and click Next. 3. Select scaled data option: Linear and click Next. 4. Enter pressure value position 1 and click Next. 5. Enter scaled variable position 1 and click Next. 6.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Right click on the device and select “Device Configuration,” then “Re-mapping” from the menu. 1. Click Next after setting the control loop to manual. 2. Choose desired primary variable then click Next. 3. Choose desired secondary variable then click Next. 4. Select Next to confirm tertiary variable setting. 5. Select Next to acknowledge the loop can be returned to automatic control. 6.
Reference Manual 00809-0100-4027, Rev AA December 2005 Loop Test Fast Keys 1, 2, 2 Rosemount 4500 The Loop Test command verifies the output of the transmitter, the integrity of the loop, and the operations of any recorders or similar devices installed in the loop. HART Communicator To initiate a loop test, perform the following procedure: 1.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Right click on the device and select “Diagnostics and Test,” then “Loop test” from the menu. 1. Click Next after setting the control loop to manual. 2. Select desired analog output level. Click Next. 3. Click Next to acknowledge output being set to desired level. 4. Check the reference meter installed in the test loop to verify that it displays the commanded output value. a.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 4. Select the back arrow from the HOME/ONLINE screen. The HART Communicator menu appears. 5. Select 1: Offline, 2: Saved Configuration, 1: Module Contents to reach the MODULE CONTENTS menu. 6. Use the DOWN ARROW to scroll through the list of configurations in the memory module, and use the RIGHT ARROW to select and retrieve the required configuration. 7. Select 1: Edit. 8. Select 1: Mark All. 9. Select F2 SAVE. 10.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Applying a User Configuration Any amount of user configurations can be created for the application. They can also be saved, and applied to connected devices or to devices in the Device List or Plant Database. NOTE When using AMS Revision 6.0 or later, the device to which the user configuration is applied, must be the same model type as the one created in the user configuration. When using AMS Revision 5.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Right click on the device and select “Configuration Properties” from the menu. 1. In the “HART” tab, use the drop down menu to select “Burst Mode ON or OFF.” For “Burst option” select the desired properties from the drop down menu. Burst options are as follows: • PV • % range/current • Process vars/crnt • Process variables 2. After selecting options click Apply. 3.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 The 4500 is set to address zero (0) at the factory, which allows operation in the standard point-to-point manner with a 4–20 mA output signal. To activate multidrop communication, the transmitter address must be changed to a number from 1 to 15. This change deactivates the 4–20 mA analog output, sending it to 4 mA. It also disables the failure mode alarm signal, which is controlled by the upscale/downscale switch position.
Reference Manual 00809-0100-4027, Rev AA December 2005 Section 4 Rosemount 4500 Operation and Maintenance Calibration for HART Protocol . . . . . . . . . . . . . . . . . . . . . . page 4-1 OVERVIEW This section contains information on commissioning and operating 4500 Pressure Transmitters. Tasks that should be performed on the bench prior to installation are explained in this section. HART Communicator and AMS instructions are given to perform configuration functions.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Table 4-1. Recommended Calibration Tasks Transmitter 4500_ G 4500_ A Bench Calibration Tasks Field Calibration Tasks 1. Set output configuration parameters: a. Set the range points. b. Set the output units. c. Set the output type. 1. Reconfigure parameters if necessary. 2. Perform low trim value section of the full sensor trim procedure to correct for mounting position effects. d. Set the damping value. 2.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Figure 4-1 also identifies the approximate transmitter location for each calibration task. Data flows from left to right, and a parameter change affects all values to the right of the changed parameter. Not all calibration procedures should be performed for each 4500 transmitter. Some procedures are appropriate for bench calibration, but should not be performed during field calibration.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Determining Calibration Frequency Calibration frequency can vary greatly depending on the application, performance requirements, and process conditions. Use the following procedure to determine calibration frequency that meets the needs of your application. 1. Determine the performance required for your application. 2. Determine the operating conditions. 3. Calculate the Total Probable Error (TPE). 4. Calculate the stability per month.
Reference Manual 00809-0100-4027, Rev AA December 2005 Choosing a Trim Procedure Rosemount 4500 To decide which trim procedure to use, you must first determine whether the analog-to-digital section or the digital-to-analog section of the transmitter electronics need calibration. Refer to Figure 4-1 and perform the following procedure: 1. Connect a pressure source, a HART Communicator or AMS, and a digital readout device to the transmitter. 2.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Zero Trim Fast Keys 1, 2, 3, 3, 1 NOTE The transmitter must be within three percent of true zero (zero-based) in order to calibrate with zero trim function. HART Communicator Calibrate the sensor with a HART Communicator using the zero trim function as follows: 1. Vent the transmitter and attach a HART Communicator to the measurement loop. 2. From the HOME screen, follow the fast key sequence for “Zero Trim.” 3.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 NOTE Select pressure input values so that low and high values are equal to or outside the 4 and 20 mA points. Do not attempt to obtain reverse output by reversing the high and low points. The transmitter allows approximately five percent URL deviation from the characterized curve established at the factory. 4. Follow the commands provided by the HART Communicator to complete the adjustment of the lower value. 5.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Recall Factory Trim— Analog Output Fast Keys 1, 2, 3, 4, 2 This command resets the transmitter analog output trim to the “as shipped” factory settings. The Recall Factory Trim—Analog Output command can be useful for recovering from an inadvertent trim, incorrect Plant Standard or faulty meter. AMS Right click on the device and select “Calibrate,” then “Recall Factory Trim” from the menu. 1.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 AMS Right click on the device and select “Calibrate,” then “D/A Trim” from the menu. 1. Click Next after setting the control loop to manual. 2. Click Next after connecting the reference meter. 3. Click Next at the “Setting fld dev output to 4mA” screen. 4. Record the actual value from the reference meter, and enter it at the “Enter meter value” screen and click Next. 5.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 a. If Yes is selected, proceed to Step 10. b. If No is selected, repeat Step 8. 10. Click Next at the “Setting fld dev output to 20mA” screen. 11. Repeat Step 8 - Step 9 until the reference meter equals the transmitter output value. 12. Select Next to acknowledge the loop can be returned to automatic control. 13. Select Finish to acknowledge the method is complete.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 NONPV LIMIT A secondary variable read by the transmitter is outside of the transmitter’s range. CURR SAT The pressure read by the module is outside of the specified range, and the analog output has been driven to saturation levels. LOOP TEST A loop test is in progress. During a loop test or 4–20 mA trim, the analog output is set to a fixed value. The meter display alternates between the current selected in milliamps and “LOOP TEST.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 SPAN FAIL The span value, set with the local span adjustment button, exceeds the maximum range down allowed for a particular range, or the pressure sensed by the transmitter exceeds the sensor limits. KEYS DISABL This message appears during reranging with the integral zero and span buttons and indicates that the transmitter local zero and span adjustments have been disabled.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Section 5 Troubleshooting OVERVIEW Table 5-1 provides summarized maintenance and troubleshooting suggestions for the most common operating problems. If you suspect malfunction despite the absence of any diagnostic messages on the HART Communicator display, follow the procedures described here to verify that transmitter hardware and process connections are in good working order. Always deal with the most likely checkpoints first.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Table 5-1. Rosemount 4500 troubleshooting table Symptom Corrective Actions Transmitter milliamp reading is zero Verify power is applied to signal terminals Check power wires for reversed polarity Verify terminal voltage is 11.
Reference Manual 00809-0100-4027, Rev AA December 2005 Appendix A Rosemount 4500 Reference Data Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1 Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-5 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-8 SPECIFICATIONS Performance Specifications For zero-based spans, reference conditions, Neobee M-20 oil fill, SST materials, 11/2 in.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Range and Sensor Limits Rosemount 4500 Sanitary Pressure Transmitter Range Limits Range 1 AP Functional Specifications Range 1 GP Range 2 Units min. max. min. max. min. max. psi kPa bar kg/cm2 0.60 4.14 0.041 0.042 30 206.8 2.068 2.109 0.6 4.136 0.04136 0.04218 30 206.8 2.068 2.109 10 68.94 0.689 0.703 150 1034 10.34 10.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Overpressure Limits Transmitters withstand the following pressure without damage: Range 1: 150 psi (10.34 bar) Range 2: 300 psi (20.68 bar) Burst Pressure Limits Range 1: 300 psi (20.68 bar) Range 2: 450 psi (31.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Alarm Configuration Rosemount High Alarm: ≥ 21.75 mA Low Alarm: ≤ 3.75 mA Custom Level (1) High Alarm: 20.2 - 23.0 mA Low Alarm: 3.6 - 3.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 DIMENSIONAL DRAWINGS FIGURE 1. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitter 11/2 inch Tri-Clamp Module 5.50 (139.7) 4.03 (102.4) 2.09 (53.1) 2.49 (63.2) 1.50 (38.1) 2.00 (50.7) A-5 Note Dimensions are inches (millimeters) 4500_01_AA, 4500_02_AA, 4500_03_AA, 4500_04_AA.EPS 3.00 (76.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 FIGURE 2. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitter 2 inch Tri-Clamp Module 5.50 (139.7) 4.03 (102.4) 2.49 (63.2) 2.09 (53.1) 1.50 (38.1) 2.50 (63.4) A-6 Note Dimensions are inches (millimeters) 4500_10_AA, 4500_11_AA, 4500_12_AA, 4500_13_AA.EPS 3.00 (76.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 FIGURE 3. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitter Fractional Line Fitting Module 5.50 (139.7) 4.03 (102.4) 2.09 (53.1) 2.49 (63.2) 0.63 (16.1) 1.50 (38.1) 1.99 (50.4) A-7 Note Dimensions are inches (millimeters) 4500_20_AA, 4500_21_AA, 4500_22_AA, 4500_23_AA.EPS 3.00 (76.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 ORDERING INFORMATION Model Transmitter Type 4500 Hygienic Pressure Transmitter Code Measurement Type G A Code 1 2 Code 2 3 Code C11 C12 C13 Code A Code A Gauge Absolute Pressure Range Gauge Absolute -14.7 to 30 psi -14.
Reference Manual 00809-0100-4027, Rev AA December 2005 Appendix B Rosemount 4500 Product Certificates Approved Manufacturing Locations . . . . . . . . . . . . . . . . . page B-1 Ordinary Locations Certifications . . . . . . . . . . . . . . . . . . . page B-1 European Directive Information . . . . . . . . . . . . . . . . . . . . page B-1 Hazardous Locations Certifications . . . . . . . . . . . . . . . . . page B-2 APPROVED MANUFACTURING LOCATIONS Rosemount Inc.
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 HAZARDOUS LOCATIONS CERTIFICATIONS North American Certifications Factory Mutual (FM) Approvals I5 Intrinsically Safe for use in Class I, II, III, Division 1, Groups A, B, C, D, E, F, and G; Temperature Code T4 (Tamb = 0 to 60°C); Intrinsically Safe for use in Class I, Zone 0 AEx ia IIC T4 (Tamb = 0 to 60°C); Non-incendive for Class I, Division 2, Groups A, B, C, and D; When connected in accordance with Rosemount drawing 04500-5001; Enc
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 N1 ATEX Type n (Pending) Certificate No. Baseefa05ATEX0092X ATEX Marking: II 3 G EEx nA nL IIC T5 (Tamb = 60°C) Ui = 42.4V MAXIMUM IP66 Special Conditions For Safe Use (x) The plastic meter cover does not meet the surface resistivity requirements and, to avoid electrostatic charging, it must not be rubbed or cleaned with solvents.
Reference Manual Rosemount 4500 B-4 00809-0100-4027, Rev AA December 2005
Reference Manual 00809-0100-4027, Rev AA 12/5/05 Rosemount 4500 Index A Address Changing . . . . . . . . . . . . . 3-24 Alarm . . . . . . . . . . . . . . . . . . . 3-13 Burst mode values . . . . . . 3-13 Failure mode values . . . . 3-11 Level configuration . . . . . 3-12 Level verification . . . . . . . 3-14 Multidrop mode values . . 3-13 Alarm direction configuration . . 2-6 Alerts . . . . . . . . . . . . . . . . . . . . 3-14 Analog output trim . . . . . . . . . . . 4-8 Approvals . . . . . . . . . . . .
Reference Manual 00809-0100-4027, Rev AA 12/5/05 Rosemount 4500 P Trim Power supply HART protocol . . . . . . . . . . 2-7 Power up . . . . . . . . . . . . . . . . . . 2-7 Power supply HART protocol 2-7 Process alerts . . . . . . . . . . . . . 3-14 Process variables . . . . . . . . . . . 3-7 Units . . . . . . . . . . . . . . . . . 3-8 Analog output . . . . . . . . . . . 4-8 Digital to Analog . . . . . . . . . 4-8 Other scale . . . . . . . . . 4-9 Full . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4027, Rev AA December 2005 Rosemount 4500 Emerson Process Management Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.) 1-800-999-9307 T (International) (952) 906-8888 F (952) 949-7001 Rosemount GmbH & Co. Shipping Address: Argelsrieder Feld 3 82234 Wessling T 49 (8153) 9390 F 49 (8153) 939172 www.rosemount.com ¢00809-0100-4027 ¤ © 2005 Rosemount Inc. All rights reserved.