Specifications
Table Of Contents
- 1.0 System Overview
- 2.0 Product Description
- 2.1 Application Software
- 2.2 Custom Software Development
- 2.2.1 SITECONFIG-SVC - SiteScan Configuration Service Agreement
- Additional Benefits
- HIGRAPHIC - Create a Graphic
- HIGRAPHICM - Modify a Graphic
- HIGRAPHICUP - Upgrade SS2000W Graphic to SSWeb Java-Based Graphic (1)
- HIGRAPHICUP-5 - Upgrade SS2000W Graphics to SSWeb Java-Based Graphics (2-5)
- TEXTMOD - Customized Modifications
- MODCONFIG-4 - Modbus Configuration
- MODCONFIG-12 - Modbus Configuration
- BACCONFIG-4 - BACnet Configuration
- BACCONFIG-12 - BACnet Configuration
- 2.2.1 SITECONFIG-SVC - SiteScan Configuration Service Agreement
- 2.3 Gateway Modules
- 2.4 SiteLink Modules
- 2.5 Site I/O Modules
- 2.6 Stand-Alone Monitoring Modules
- 2.7 Module Accessories
- 2.8 ARCnet Communication Enhancement Devices
- 2.8.1 ARC156-KIT - ARCnet Kit
- 2.8.2 Other ARCnet Parts
- ARCDIAG485 - ARCnet156 Diagnostics Board
- ARCDIAG485WO - ARCnet156 Diagnostics Board Without Enclosure
- ARCPROT485 - ARCnet156 Surge Protection Board
- ARCPROT485WO - ARCnet156 Surge Protection Board Without Enclosure
- ARCREP485 - ARCnet156 Repeater Board (Signal Booster)
- ARCREP485WO - ARCnet156 Repeater Board Without Enclosure
- 2.9 Third-Party Interfaces
- 3.0 Application and Configuration
- 4.0 Upgrading SiteScan 2000 Systems to SiteScan Web
- 5.0 Third-Party and Building Management Interfaces
- 5.1 SiteScan Web and BACnet/IP to BMS
- 5.2 BACnet/IP to BMS Without a SiteScan Web Front-End
- 5.3 BMS Front-End Interfacing to Liebert Equipment by EIA-485 Modbus
- 5.4 SiteTPI-E with OpenComms NIC (or OpenComms 485)
- 5.5 Basic SiteTPI-E with Third-Party Equipment
- 5.6 SiteTPI-E and Third-Party Equipment with Different Modbus Protocol
- 6.0 ARCnet156
- 7.0 Wiring Guidelines
- Appendix A - Terminology

Third-Party and Building Management Interfaces
24
5.2 BACnet/IP to BMS Without a SiteScan Web Front-End
5.2.1 Target Application
A typical application might be:
• Customer has a BMS front-end and does not want a SiteScan Web front-end.
• Two new computer rooms need to be monitored by BMS.
• Each computer room will have the following:
• 3 Liebert environmental units
• 1 STS2/PDU
• 2 NPower UPSs
• 4 analog sensors
• 2 strobe lights for alarm conditions
• One local user is allowed.
5.2.2 Description
This configuration is ideal for customers who have a current investment within their BMS and do not
want another front-end for monitoring. The SiteGate-E gateway module natively communicates
BACnet/IP to the SiteScan Web front-end. This same protocol is available to any BMS front-end that
supports BACnet/IP.
5.2.3 Bill of Materials
Figure 11 BACnet/IP to BMS without SiteScan Web front-end
Table 13 Bill of materials: BACnet/IP to BMS (without SSWeb front-end)
Qty. Mktg. P/N Description
2 SITEGATE-E 32-bit Ethernet-ready gateway module
8 XFMR24 Transformers for 120/24VAC module power supply
2 SITELINK-12 SiteScan interface module to 12 Liebert units
2 ARC156-KIT PROT485, DIAG485 and terminating resistors with enclosure
2 SITEIO1616 Site I/O module, 16 universal inputs and 16 digital outputs
Note: The bill of materials does not include LGS startup part numbers. Most LGS startup part
numbers are added automatically when ordering.
Ethernet
SiteGate-E
SiteIO 16/16
ARC156-Kit
SiteLink-12
Computer Room 1
BMS
front-end
SiteGate-E
SiteIO 16/16
ARC156-Kit
SiteLink-12
Computer Room 2
Ethernet
BMS
front-end
BACnet/IP
BMS
equipment
EXISTING
SYSTEM
UPGRADED
SYSTEM