Specifications

Table Of Contents
Upgrading SiteScan 2000 Systems to SiteScan Web
22
4.4 Upgrading SS2000W to Full SiteScan Web
A full SiteScan Web upgrade of an existing SiteScan 2000W system permits the customer to take full
advantage of the SiteScan Web system.
This upgrade requires replacing each DCLan or SiteGate-232 module with a SiteGate-E module. All
graphics must be upgraded.
4.4.1 Target Application
A typical application for this upgrade might be:
Customer wants to upgrade a SiteScan 2000W system.
Existing system uses a SiteGate-232.
System has four existing floor plans.
CMnet has two DC12-i422 modules, one RCM10U I/O modules and two SiteLink-12 modules.
4.4.2 Description
To upgrade a SS2000W system to a full SiteScan Web System, all hardware, including the gateway
module, must be ARCnet-compatible. All modules that are not ARCnet-compatible must be replaced.
Next, the CMnet wire must be replaced with a Magnum cable (A3-ARC-156-2). Also, you must order
upgrades to convert the customer’s current graphics to SiteScan Web Java-based graphics.
Be sure to make a note on the Site Survey that the job should be built as a full SiteScan
Web system.
4.4.3 Bill of Materials
Figure 9 Upgrading from SS2000W to full SiteScan Web
NOTE
Customers may have to replace the computer running SS2000W if it does not meet the
minimum operating requirements for SiteScan Web (see Table 1 in 2.1.1 - SSWEB - SiteScan
Web Base Product). In addition, that computer must be connected to an Ethernet network.
Table 11 Bill of materials: Full SiteScan Web upgrade from SS2000W
Qty. Mktg. P/N Description
1 SSWEBUP SiteScan Web upgrade of SS2000W or SS2W
1 SITEGATE-E 32-bit Ethernet-ready gateway module
4 XFMR24 Transformers for 120/24VAC module power supply
1 HIGRAPHICUP-5 Upgrades up to five (5) SS2000W graphics
1 ARC156-KIT PROT485, DIAG485 and terminating resistors with enclosure
1 SITEIO10 Site I/O 10/0, Universal Input Module - 10 points
2 SITELINK-12 SiteScan interface module to 12 Liebert units
Note: The bill of materials does not include LGS startup part numbers. Most LGS startup part numbers are added automatically
when ordering.
Note: The bill of materials does not include the cost of replacing the CMnet wire to ARCnet wire.
Replace
with
SiteLink-12
SiteLink-12
Ethernet
SiteGate-E
Add
DC
Lan
DC12-i422
DC12
DC12-i422
DC12
RCM10U
Site I/O 10/0
SiteLink-12
EXISTING
SYSTEM
UPGRADED
SYSTEM
SiteLink-12