User manual

52 Chapter 8 Product Specifications
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
8.4 Electrical Characteristics (Input Rectifier)
Table 8-4 Rectifier AC input (mains)
Item Unit Rated power (kVA)
30 40 60 90, 100 120 150, 60 200
Rated AC input voltage
1
Vac 380/400/415 (3-phase and sharing neutral with the bypass input)
Input voltage range
2
Vac 228 ~ 437
Frequency
2
Hz 50/60 (tolerance: 40Hz ~ 70Hz)
Power factor kW/kVA, full load (half
load)
0.99 (0.98)
Input power kVA rated
3
(maximum
4
) 30
(34.5)
40
(46)
60
(69)
90
(103.5)
120
(138)
150
(173)
180
(207)
Input current A rated
3
(maximum
4
) 45 (54) 55
(70)
90
(108)
135
(162)
180
(216)
225
(270)
270
(320)
Harmonic current distortion THDI% FL 3
Duration of progressive
power walk-in
s 10s to reach full ratd current (selectable 5s through 30s in 5-second
intervals)
Note:
1. Rectifiers operate at any of the rated supply voltages and frequencies without further adjustment.
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged
battery.
3. IEC62040-3: at rated load and input voltage 400V, battery charged.
4. IEC62040-3: at rated load and input voltage 400V, battery charging at maximum rated power
8.5 Electrical Characteristics (Intermediate DC Circuit)
Table 8-5 Battery
Item Unit Rated power (kVA)
30 40 60 90, 100 120 150, 160 200
Battery bus voltage Vdc Nominal: 360 (VRLA float charge is 405V); range: 300 ~ 576
Quantity of
lead-acid cells
Maximum 40 x 6-cell 12V blocks
Minimum 30 x 6-cell 12V blocks
Float voltage V/cell (VRLA) 2.25 (selectable from 2.2V/cell to 2.3V/cell)
Constant current and constant voltage charge mode
Temperature
compensation
mV/°C/cl –3.0 (selectable from 0 to –5.0 around 25°C or 30°C, or inhibit)
Ripple voltage % V float 1
Ripple current % C
10
5
Boost voltage V/cell (VRLA) 2.35 (selectable from 2.30V/cell to 2.40V/cell)
Constant current and constant voltage charge mode
Boost control
Float-boost current trigger 0.050C
10
(selectable from 0.030 to 0.070)
Boost-float current trigger 0.010C
10
(selectable from 0.005 to 0.025)
24hr safety time timeout (selectable from 8hr to 30hr)
Boost mode inhibit also selectable
EOD voltage
V/cell (VRLA)
1.63 (selectable from 1.60V/cell to 1.750V/cell)
3
Automatic inverse, EOD voltage × discharge current mode
(the EOD voltage increases at low discharge currents)
Battery charge V/cell
2.4 (selectable from 2.30V/cell to 2.40V/cell)
Constant current and constant voltage charge mode
Programmable automatic trigger or inhibit of boost mode
Battery
charging power
1
and max charging
current
(adjustable)
2
kW 4.5 6 9 13.5 18 22.5 27
A 11 14.7 22 33 44 55 66