User manual
Chapter 8 Product Specifications 51
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
Chapter 8 Product Specification
The chapter provides the UPS specifications.
8.1 Conformity And Standards
The UPS has been designed to conform to the European and international standards listed in Table 8-1.
Table 8-1 European and international standards
Item Normative reference
General and safety requirements for UPS used in operator
access areas
EN62040-1-1/IEC62040-1-1/AS62040-1-1
Electromagnetic compatibility (EMC requirements for UPS EN62040-2/IEC62040-2/AS62040-2 (C2 type)
Method of specifying the performance and test requirements of
UPS
EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series
and 60529)
8.2 Environmental Characteristics
Table 8-2 Environmental characteristics
Item Unit Rated power (kVA)
30 40, 60 90, 100, 120 150, 160 200
Noise within 1m (in the front) dB 56 58 60 62 66
Altitude m
≤1000, derate power by 1% per 100m between 1000m and 2000m
Relative humidity %RH 0 ~ 95, non condensing
Operating temperature °C 0 ~ 40; battery life is halved for every 10°C increase above 20°C
Storage and transport temperature for UPS °C -20 ~ 70
Recommended battery storage
temperature
°C -20 ~ 30 (20°C for optimum battery storage)
Over voltage category IEC 60664-1 level 2
Pollution degree IEC 60664-1 level 2
8.3 Mechanical Characteristics
Table 8-3 Mechanical characteristics
Item Unit Rated power (kVA)
30
40
,
60
90, 100 120 150, 160 200
Dimensions (W × D × H) mm 600 × 843 × 1400 600 × 843 × 1600
Weight (excluding battery) kg 200 234 268 302 336 380
Color Charcoal Grey ZP7021 / RAL 7021
Protection degree, IEC(60529) IP20 (front door open or closed)