32 Chapter 5 Operator Control And Display Panel
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
Chapter 5 Operator Control And Display Panel
This chapter expands the functions and use of the components on the operator control and display panel of the UPS,
provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and
UPS alarm list, and tells how to select language and change the current data and time.
5.1 Introduction
The operator control and display panel is located on the front door of the UPS. It is the access point for operator
control and monitoring of all measured parameters, UPS and battery status and alarms. The operator control and
display panel is divided into three functional areas: mimic power flow chart, LCD display with menu keys, control keys,
as shown in Figure 5-1. The components on the operator control and display panel are described in Table 5-1.
LCD display with menu keys
EPO
INVERTER ON INVERTER OFF
FAULT CLEAR SILENCE ON / OFF
8
Control keys
1
2
45
3
6
7
Mimic power flow chart
STATUS
Lieber
t NX
20
08
-
1
0
-
3
1
1
2
:
3
0
:
3
6
1
5
0
kV
A
-3 X3
单机
在线
?
旁路输入主路输入
相电压 (V )
相电流 (A )
频率 (H z )
线电压 (V )
功率因数
A( AB )
220
20 .5
50 .1
380
0.99
B(BC )
220
20 .5
50 .1
380
0.99
C(CA )
220
20.5
50.1
380
0.99
主路空开闭合 01 - 12
手动开机
主路逆变供电 01 - 22
交流输出
单机在
线
NXr
15
0
kVA
1
6
:
2
1
:
1
7
交流输出
A(AB) B(BC) C(CA)
相电压(V)
相电流(A)
频率(Hz)
线电压(V)
功率因数
220 220 220
20.5 20.5 20.5
50.1 50.1 50.1
380 380 380
0.99 0.99 0.99
F1
F3 F4
F5F2
Figure 5-1 Operator control and display panel
Table 5-1 Description of operator control and display panel
Part No. Function Key Function
1 Rectifier indicator
EPO EPO switch
2 Battery indicator INVERTER ON Inverter start switch
3 Bypass indicator INVERTER OFF Inverter shutdown switch
4 Inverter indicator FAULT CLEAR Fault reset switch
5 Output indicator SILENCE ON/OFF Audible alarm silencing switch
6 Status indicator F1 ~ F5 LCD menu keys
7 Buzzer
8 EPO switch cover
5.1.1 Indicators
The indicators mounted on the mimic power flow chart represent the various power paths and current UPS
operational status. The indicators are described in Table 5-2.
Table 5-2 Indicator description
Indicator State Description
Rectifier indicator
Solid green Rectifier in normal operation
Flashing green Mains input normal, but rectifier not operating
Solid red Rectifier fault
Off Rectifier not operating, mains input abnormal