User manual

Chapter 2 Battery 19
NXr UPS Module And Parallel System 30kVA ~ 200kVA User Manual
Figure 2-1 External battery cable connection
40
46.7
46.746.7
46.7
126.5
384
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery Battery
Lead out the battery neutral
cable from here on the third layer
Separator
Red
Battery
compartment
Black
Blue
Red
Black
Blue
Figure 2-2 Internal battery cable connection (NXr 30K-B)
2.4 Battery Maintenance
The battery supplied by Emerson complies with the safety requirements of IEC 62040-1:2008. For the battery
maintenance and maintenance precautions, refer to the relevant manual provided by the battery manufacturer and
observe applicable local regulation e.g. AS2676:1993, IEEE-Std-1188-2005.
Note
1. Periodically check the screws of the battery terminals for loose connection. If there is any loose screw, tighten it immediately.
2. Check that all safety devices are present and that their functions are normal. Check that the battery management parameters
are set correctly.
3. Measure and record the air temperature inside the battery room.
4. Check the battery terminals for damage and heating. Check the battery enclosure and terminal covers for damage.