User manual
UPS Specifications
87
10.4 UPS Electrical Characteristics
Table 27 UPS terminal
Input (for single-input unit)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10 28 35 42 45 6M (1/4") 54105 62204
15 42 53 63 70 6M (1/4") 54106 62204
20 56 70 84 90 6M (1/4") 54107 62204
30 83 104 125 125 6M (1/4") 54152 62205
Rectifier input (for dual input unit only)
Unit
Rating
Nominal
Input
Current
Maximum
Input
Current
OCP
Current
OCP
Device
Rating Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10 25 31 37 40 6M (1/4") 54130 62204
15 37 47 57 60 6M (1/4") 54106 62204
20 50 63 76 80 6M (1/4") 54107 62204
30 75 94 113 125 6M (1/4") 54152 62205
Bypass input (for dual input units)
Unit
Rating
Nominal
Input
Current OCP Current
OCP
Device
Rating Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole
54000
Lug T&B
One Hole
REDDY
10 28 35 35 6M (1/4”) 54105 62204
15 42 53 60 6M (1/4”) 54106 62204
20 56 70 70 6M (1/4”) 54107 62204
30 83 104 110 6M (1/4”) 54152 62205
Output
Unit
Rating Nominal Output Current
OCP
Current
OCP
Device
Rating Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10 28 35 35 6M (1/4") 54130 62204
15 42 53 60 6M (1/4") 54106 62204
20 56 70 70 6M (1/4") 54106 62204
30 84 105 110 6M (1/4") 54108 62205
Battery
Unit
Rating Battery Current
OCP
Current
OCP
Device
Rating Bolt Size
Maximum Recommended Lug
Lug T&B
One Hole 54000
Lug T&B
One Hole REDDY
10/15 55 55 70 6M (1/4") 54106 62204
20/30 110 110 125 8M (5/16") 54153 62212
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions.
3. UPS input and bypass cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full
load current (continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to
be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 2005.
7. Wiring requirements:
a. AC Input: 3-phase, 4-wire, plus ground output.
b. AC Output: 3-phase, 3- or 4-wire, plus ground
8. All wiring is to be in accordance with national and local electric codes.