General Features
While every precaution has been taken to ensure accuracy and completeness in this brochure, Liebert Corporation assumes no responsibility, and disclaims all liability
for damages resulting from use of this information or for any errors or omissions. © 2002 Liebert Corporation. All rights reserved throughout the world. Specifications subject
to change without notice. All names referred to are trademarks or registered trademarks of their respective owners.
General & Environmental
Unit Rating kVA 481216 20
kW 2.8 5.6 8.4 11.2 14
Conducted and Radiated EMC Levels EN50091-2 Class A
Compliant Safety Standards EN50091-1, EN 60950, CE, Low Voltage Directive
Compliant Immunity Standards EN61000 - 4 - 2,3,4,5,6
8 Bay 12 Bay
Dimensions: Width mm 508
Dimensions: Depth mm 711
Dimensions: Height mm 1016 1372
Environmental
Operating Temperature (max) 0°- 40°
Relative Humidity % 0 - 95% non-condensing
Maximum Operating Altitude m 3000
Nominal Heat Dissipation W 311 @ 622 @ 933 @ 1244 @16kVA 1265 @ 20kVA
4kVA 8kVa 12kVA
Acoustic Noise Level dBA <62@ 1m
Input Data
Nominal Input Voltage VAC 220/230/240 for 1x1 units
380/400/415 for 3x1 units (12 bay only)
Power Factor cos .98 for 1x1 units
.80 for 3x1 units
Input Frequency (nominal) Hz 50
Input Frequency Range Hz 40 - 70
Battery Module
Number Of Lead Acid Batteries 10
Number Of Battery Cells 60
Battery Capacity AH 9
Autonomy Time (full load) minutes 7 (with an equal number of Battery & Power modules
in non-redundant configuration)
Maximum Charge Current (full load) A 3
Nominal Voltage VDC 120
Recharge Time Hr 3 - 5 (90% capacity)
Output Data Units
Output Voltage VAC 220/230/240 (220 requires output transformer)
Voltage Regulation % ±3
Voltage Stability (100% step load) % ±7
Recovery Time msec 96
Voltage distortion % <3% THD linear load
<7% THD non-linear load
Output Frequency Hz 50
Efficiency at 100% load % 91
Output Overload Capability %
NOTE: 3x1 units available in 12-Bay frames only. 16kVA 1x1 requires 12-Bay frame. 20kVA rating available for 3x1 models only.
>100% - 110% operates indefinitely
111% - 150% operates for 8 sec
151% - 200% operates for 0.25 sec
>201% operates for 2 cycles
for 3x1 units
>100% - 110% for 10 min.
111% - 150% operates for 8 sec
151% - 200% operates for 0.25 sec
>201% operates for 2 cycles
for 1x1 units