2.3 Configure an RPC2 Communications Module for Static IP
The RPC2 communications module is factory-set for DHCP, making it ready for service immediately.
The module can be configured for operation on a network using static IP or BootP.
To configure a module for a network that uses static IP:
1. Insert an additional Ethernet cable (not included) into the module’s Link port (see Figure 1
for the port location).
2. Insert the other end of the Ethernet cable into a laptop.
3. Configure the laptop’s IP settings to communicate on a 192.168.1.X network.
IP address: 192.168.1.9
Subnet mask: 255.255.255.252
Default gateway: 192.168.1.1
4. Open a Web browser to enter the IP address of the Link Port.
5. When prompted for a username and password, enter the default login and password—admin for
both (case-sensitive)—and click the Login icon or press the enter key.
6. Click the System tab, then click Settings>Network in the navigation tree.
7. Click the Edit icon in the right pane .
8. The default Speed/Duplex for the Ethernet port is Auto 1000 Mbs/Full Duplex (automatic). To
change this, choose from the Speed/Duplex drop-down list.
9. Choose the IPV4 Boot Mode: Static or DHCP. (The default is DHCP.)
10. Click the Save icon, , to save the change or click the Cancel icon to cancel the change.
11. Configure the IP Address, Subnet Mask and Default Gateway in the System tab; see your
network administrator for these settings.
12. To complete the configuration, click the Reboot icon in System tab>Settings.
Use Table 3 to make changes to the cards in the array using the Link port.
NOTE
The card’s Link port should be used only for local configuration through interconnection to a
laptop. Do not connect the cable from the Link port to your company LAN, to an Ethernet
network or to similar a network.
NOTE
RPC2 communications module configures sibling connections automatically but must be
rebooted if the connection order is changed. For information about sibling connections, refer to
2.5 - Create a Rack PDU Array
.
Table 3 Laptop IP settings for RPC module addresses
IP Address Rack PDU 1 Rack PDU 2 Rack PDU 3 Rack PDU 4
Laptop Computer 192.168.1.9 192.168.1.5 192.168.1.1 192.168.1.13
Link Port 192.168.1.10 192.168.1.6 192.168.1.2 192.168.1.14
Subnet Mask 255.255.255.252 255.255.255.252 255.255.255.252 255.255.255.252
X