White Paper
5
Figure 4. -48V DC power as typically implemented in telecommunications central offices.
Figure 5. A row-based DC UPS eliminates the long copper runs and is optimized for the data center.
Figure 2. In eco-mode, incoming power bypasses the inverter to increase UPS system efficiency.
PDU PSU
Transformer
Rectifier
Bypass
Battery
Double Conversion UPS
Server
480V AC 480V AC 208V AC 12V DC
AC
DC
DC
DC
Load
Inverter
PDU PSU
Transformer
Rectifier
Bypass
Battery
Inverter
Double Conversion UPS
Server
Figure 1. Typical 480V AC to 208V AC data center power system configuration.
480V AC 480V AC 208V AC 12V DC
AC
DC
DC
DC
Load
Figure 3. 480V AC to 277V AC data center power system configuration.
PDU
PDU
PSU
Rectifier
Bypass
Battery
Double Conversion UPS
Server
480V AC 480V/277V AC 277V AC 12V DC
AC
DC
DC
DC
Load
Inverter
Figure 4. -48VDC power as typically implemented in telecommunications central offices.
PSU
Switch
12V DC
DC
DC
Load
Battery
480V AC 48V DC 48V DC
Rectifiers
(N+m)
Figure 5. A row-based DC UPS minimizes the amount of copper and floor space required for installation in the data center.
PSU
Battery
PDU
Row-Based DC UPS Server
480V AC 48V DC 12V DC
DC
DC
Load
Rectifiers
(N+m)
Figure 2. In eco-mode, incoming power bypasses the inverter to increase UPS system efficiency.
PDU PSU
Transformer
Rectifier
Bypass
Battery
Double Conversion UPS
Server
480V AC 480V AC 208V AC 12V DC
AC
DC
DC
DC
Load
Inverter
PDU PSU
Transformer
Rectifier
Bypass
Battery
Inverter
Double Conversion UPS
Server
Figure 1. Typical 480V AC to 208V AC data center power system configuration.
480V AC 480V AC 208V AC 12V DC
AC
DC
DC
DC
Load
Figure 3. 480V AC to 277V AC data center power system configuration.
PDU
PDU
PSU
Rectifier
Bypass
Battery
Double Conversion UPS
Server
480V AC 480V/277V AC 277V AC 12V DC
AC
DC
DC
DC
Load
Inverter
Figure 4. -48VDC power as typically implemented in telecommunications central offices.
PSU
Switch
12V DC
DC
DC
Load
Battery
480V AC 48V DC 48V DC
Rectifiers
(N+m)
Figure 5. A row-based DC UPS minimizes the amount of copper and floor space required for installation in the data center.
PSU
Battery
PDU
Row-Based DC UPS Server
480V AC 48V DC 12V DC
DC
DC
Load
Rectifiers
(N+m)
Today, telephone central offices
(exchanges) are still powered by -48V DC.
These facilities exhibit levels of availability
as high as 9-nines, as confirmed in a study
of 23,000 DC power systems over 10 years
by NTT Facilities
1
.
In most telecommunications installations, the
48V DC power system is deployed as three
distinct elements as shown in Figure 4:
1. 480V AC to -48V DC modular
power system
2. Battery banks for extended run time
(at least 8 hours)
3. Load distribution cabinets (BDFB/PDU)
These elements are connected with large
copper bus bars and wires routed around
the facility to distribute power directly to
-48V power supplies at the point of use. The
power supplies step the voltage down to
12V and lower DC voltages for internal uses.
It is easy to see the benefits of this
approach when applied to the data center.
Downstream of the AC/DC rectifiers, the
power is completely isolated from the
mains and is considered “safety extra low
voltage” (SELV) per IEC/UL 60950 and can
be maintained live by trained personnel.
In addition, there is no need to derate
capacity to account for phase balancing or
harmonics, which are not a factor with DC
power. Personnel safety is also improved
when servicing equipment in the rack
because arc flash is not a concern at -48V.
However, unlike telecommunications cen-
tral offices, data centers are not designed
with large copper bus bars to distribute
DC power to racks. Fortunately, with new
row-based DC topologies, these large
copper runs are no longer necessary. In
this row-based configuration, power is
converted from AC to DC very close to
the point of use, which decreases the
conductor size and cost [see Figure 5].
Data centers are entering a new stage of
maturity where the emphasis is on reliably
delivering more computing capacity to
the organization at lower cost and with
reduced power consumption. Row-based
DC power represents a practical and
affordable solution for reducing data
center complexity, increasing efficiency
and enabling growth.
Historical Background
48V DC power has a long history in tele-
communication networks. It is inherently
simple and reliable with few conversion
stages to the point of use. In Alexander
Graham Bell’s day, 48V DC was chosen as
the standard for two reasons:
1. DC power was felt to be more reliable
than AC because it could be directly
connected to backup batteries during
grid outages;
2. 48V was considered the optimal
tradeoff between transmission
distance and human safety because
it is considered safe to touch during
maintenance or accidental exposure.
A Practical Approach to DC in the Data Center