Technical Manual
NetSure™ ITM with eSure™ Technology
Site Planning Data and System Drawings — 48V DC UPS
Spec. No: 582145500 Section 6037
Model: NetSure™ ITM Issue AC, April 8, 2013
8
3.1.4 Bottom Cable Entry
Battery
Compartment
BFU
Distr.
Distr.
Raised Floor
Hot Aisle
Cold Aisle
A
Air Flow
Note 2
Side View
Support
Stand
½” (12mm) Floor
Anchoring Bolts
(4 places)
Top
Front
Notes:
1. Dimensions are in inches (millimeters).
2. Do not block air intake openings.
3. Minimum under floor space for underfloor
output cable runs: A = 1f (300mm).
4. Run cables not to block air openings for battery
cooling.
Battery
Compartment
Conduits for
AC Inputs
DC Power System
Compartment
35.43
(900)
17.72 (450)
8.86
(225)
9.84
(250)
19.68
(500)
9.84
(250)
8.86
(225)
Optional Floor
Opening for
Battery Cooling
PCUs
PCUs
PCUs
PCUs
PCUs
PCUs
P/N 547823
36” Tall Floor Stand
P/N 547822
24” Tall Floor Stand