Technical Manual

NetSure™ ITM with eSure™ Technology
Site Planning Data and System Drawings 48V DC UPS
Spec. No: 582145500 Section 6037
Model: NetSure™ ITM Issue AC, April 8, 2013
5
3 SYSTEM OUTLINE DRAWINGS
3.1 Mechanical Installation and Outline Drawings
3.1.1 Individual Cabinet Mechanical Data
3.1.2 System Configurations
23.62
(600)
84.33
(2142)
top
cabled
84.72
(2152)
bottom
cabled
Battery Compartment
Conduits for
AC Inputs
41.34
(1050)
DC Power System
Compartment
Z
X
Y
Top Cabled Version
X = 11.81 (300)
Y = 26.38 (670)
Z = 36.61 (930)
Bottom Cabled Version
X = 11.81 (300)
Y = 26.38 (670)
Z = 40.55 (1030)
CENTER OF GRAVITY
26.38
(670)
CG
11.81
(300)
(Bottom
cabled)
CG
11.81
(300)
36.61
(930)
40.55
(1030)
CG
(top
cabled)
23.62
(600)
Battery Compartment
Conduits for
AC Inputs
41.34
(1050)
DC Power System
Compartment
26.38
(670)
CG
11.81
(300)
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
Top View
Top View
Front View
Notes:
1. Dimensions are in inches (millimeters).
2. Weight (fully loaded): 2925 lbs / 1325 kg.
3. Heat Rejection: 9554 BTU/h at full load (per module).
4. May be installed on concrete slab or raised floor.
System can be expanded either to
the left or the right of the Primary Module.
Single Module
70kW (full)
64kW (n+1)
Two Modules
140kW (full)
134kW (n+1)
Three Modules
210kW (full)
204kW (n+1)
Four Modules
280kW (full)
274kW (n+1)