Technical Manual

NetSure™ ITM with eSure™ Technology
Site Planning Data and System Drawings 48V DC UPS
Spec. No: 582145500 Section 6037
Model: NetSure™ ITM Issue AC, April 8, 2013
10
4 CONNECTON DETAILS
4.1 Bottom Cable Entry Electrical Connection Detail
DETAIL E
2"
RECOMMENDED COUPLING:
RACO TYPE 2628
(GRAINGER 3LV08) OR
THOMAS BETTS TYPE
TK126US
COMMUNICATION LINKS BETWEEN CABINETS:
1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC.
2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED.
3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED.
NOTE
1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES START WHITH INNER ROW FIRST.
2. THE DC DISTRIBUTION GROUND/RETURN BUSBAR MUST BE CONNECTED VIA A SOLID
SINGLE-POINT GROUNDING LEAD TO THE MAIN BUILDING GROUND. REFER TO NEC,
TABLE 250-122 FOR GROUNDING CONDUCTOR SIZE.
DETAIL D
ENTESC
USB
RJ45
USB
INPUT AC CONDUIT(S)
SEE DETAIL E
CONTROLLER
SEE DETAIL D
INPUT AC CONNECTION
SEE DETAIL A
INPUT AC CABLE
ROUTING
CABINET GROUNDING
SUITABLE CABLE LUGS
WITH HOLE DIA 3/8" (M10)
TYPICAL LUG THOMAS
& BETTS TYPE 54136
RECOMMENDED TORQUE
407-434 in-lbs (46-49 Nm).
SIDE PLATES ARE ONLY
DELIVERED ON MAIN
CABINET. SHALL BE
MOVED TO THE LAST
EXTENSION CABINET IN
A ROW
1"
SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)
TYPICAL LUG THOMAS & BETTS TYPE 54209
RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)
DETAIL C (Circuit Breaker Option)
1
SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10)
TYPICAL LUG THOMAS & BETTS TYPE 54109
RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm)
DETAIL B (Circuit Breaker Option)
1 .75 "
1.5
DETAIL C (Fuse Option)
S UIT AB L E C AB LE LU GS W IT H H OLE D IA 1 /2" ( M12)
TY P IC AL LU G T H O MA S & B E TT S T Y P E 54282 (35 0kcm il)
R E C OM M E N D E D TOR QU E 690-743 in-lbs (78-84 Nm)
1 .75 "1.7 5 "
DETAIL B (Fuse Option)
S U IT A BL E C A B LE L U GS W IT H H OL E D IA 1/2" ( M 1 2)
TY P IC AL LU G T H O MA S & B E TT S T Y P E 54282 (35 0kcm il)
R E C OM M E N D E D TOR QU E 690-743 in-lbs (78-84 Nm)
NEGATIVE BUSBAR
SEE DETAIL C
(LOAD)
POSITIVE BUSBAR
SEE DETAIL B
(RETURN)
INPUT GROUNDING
CONNECTION
LUGS 5/16" (M8)
TYPICAL LUG THOMAS &
BETTS TYPE 54109
RECOMMENDED TORQUE
204-221 in-lbs (23-25 Nm)
DETAIL A
ONE OR TWO AC CIRCUIT BREAKERS,
NO LUGS NEEDED.
MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3)
RECOMMENDED TORQUE 124 in-lbs (14 Nm)
factory wiring
L1 L2 L3
AC IN A
L1 L2 L3
AC IN B
GND
Stud
GND
Stud