NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS Section 6037 (Issue AC, April 8, 2013) Specification Number: 582145500 Model: NetSure™ ITM Contents 1. Site Planning Data 2. One Line Diagram 3. System Outline Drawings 4.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 1 SITE PLANNING DATA 1.1 Technical Specifications Spec.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 1.2 Battery Run Times Spec.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 2 ONE LINE DIAGRAM PRIMARY DC UPS MODULE (1) AC Input A AC Input B (Optional) EXPANSION DC UPS MODULES (2-4) AC Input A AC Input B (Optional) AC Circuit Breakers (Note 3) AC Circuit Breakers (Note 3) Internal COM-link Controller and Communication Controller and Communication Current Transformer Current Transformer PCU Breakers (Note 4) PCU Breakers (Note 4) PCU PCU PCU PCU LVD PCU PCU LVD Battery Shu
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 3 SYSTEM OUTLINE DRAWINGS 3.1 Mechanical Installation and Outline Drawings 3.1.1 Individual Cabinet Mechanical Data DC UPS MODULE WITH BOTTOM FEED DC DISTRIBUTION DC UPS MODULE WITH TOP FEED DC DISTRIBUTION Battery Compartment Battery Compartment CG CG Conduits for AC Inputs 41.34 (1050) 26.38 (670) 41.34 (1050) DC Power System Compartment 26.38 (670) DC Power System Compartment Conduits for AC Inputs 11.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 3.1.3 Main Components 3.1.3.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 3.1.3.2 Top Cabled Configuration - Circuit Breaker Load Distribution (Standard) AC Input Conduit Openings Battery Return and Load Return (Battery return leads factory connected and routed to Battery Compartment.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 3.1.4 Bottom Cable Entry Notes: 1. Dimensions are in inches (millimeters). 2. Do not block air intake openings. 3. Minimum under floor space for underfloor output cable runs: A = 1f (300mm). 4. Run cables not to block air openings for battery cooling. Battery Compartment Conduits for AC Inputs DC Power System Compartment Hot Aisle Cold Aisle Top PCUs PCUs PCUs PCUs PCUs PCUs Air Flow Battery Compartment BFU Distr.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 3.1.5 Top Cable Entry Hot Aisle Cold Aisle Battery Compartment Distr. DC Power System Compartment AC Input Conduit Openings Openings for Output Cables Distr. Air Flow Top Battery Compartment PCUs PCUs PCUs PCUs PCUs PCUs BFU Concrete Floor (slab) Side View Cable Tray Note 2 Cable Tray Supports if Mounted on Top of Module Front Cable Run 35.
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 4 CONNECTON DETAILS 4.1 Bottom Cable Entry Electrical Connection Detail DETAIL B (Circuit Breaker Option) CABINET GROUNDING SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54136 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm).
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS 4.2 Top Cable Entry Electrical Connection Detail CABINET GROUNDING SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54136 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm).
NetSure™ ITM with eSure™ Technology Site Planning Data and System Drawings — 48V DC UPS Spec.