Brochure

11
eSure
PCU (R48-6000Ne) Technical Specifications
DC Output
Output Power 5833W maximum
Regulation Steady state output voltage remains within +/-0.25% for any combination of input voltage from 5% to 100% load
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 100 mv rms per Telcordia GR-947-CORE
Psophometric Noise Does not exceed 1 mv from 10% to 100% load
Protection
Current Limiting The output current is limited to 110 amps
Over Current Internal fuse
Physical Characteristics
Mounting Plug-in installation, hot swappable
Dimensions (H x W x D) – in. (mm) 3.36 x 8.83 x 14.62 (85.5 x 224.5 x 371.5)
Weight – lb. (kg) 22 (10)
Peace of mind. It’s confidence you’ve done everything possible to assure system
uptime. It’s confidence the DC UPS you rely on is operating at peak performance.
Its confidence you’ve selected the best partner available to sustain your critical
network infrastructure. That is Emerson Network Power.
Battery Back-up Time (minutes)
DC UPS
Load
Single module
70kW
Two modules
140kW
Three modules
210kW
Four modules
280kW
10kW 130 300 480 630
20kW 55 130 210 300
30kW 28 90 130 180
40kW 17 55 90 130
50kW 12 41 70 100
64kW 7 24 50 75
70kW 3 21 43 69
80kW 17 34 55
90kW 14 27 47
100kW 12 22 40
110kW 10 19 34
120kW 8 17 28
134kW 6 16 25
140kW 3 14 22
150kW 12 19
160kW 10 17
170kW 9 15
180kW 8 14
190kW 7 13
204kW 4 11
210kW 2 10
220kW 9
230kW 9
240kW 8
250kW 7
260kW 6
274kW 3
280kW 1