Installation Manual
NetSure
™
9500 120kW 400V DC Power System
Installation Manual, IM584001200 (Issue AA, April 14, 2014)
Spec. No: 584001200 Code: IM584001200
Model No: 9500 Issue AA, April 14, 2014
[16 of 25]
Figure 15. Distribution Module/Bay DC Load Connections, DC Input Connections, and Interconnecting Two (2) DC Load Distribution Panels
Rear
Front
Positive (+)
Bus
Negative (-)
Bus
Distribution
Panel
Distribution
Panel
Front door removed in
illustration for clarity only.
Distribution Module/Bay
584001200 List 07
Positive (+)
Negative (-)
Recommended Torque:
84 in-lbs (9.5 Nm)
±200V DC
Customer
Load Connections
to DC Distribution
Circuit Breakers
(M6 studs on
16mm [5/8”] centers)
(left and right sides)
Torque these
Connections:
108 in-lbs (12 Nm)
Customer DC Input Connections
to Load Distribution Panels
(M8 studs on 25mm [1”] centers)
Recommended Torque: 108 in-lbs (12 Nm)
Interconnecting Two (2)
Load Distribution Panels
Positive (+) Bus
Negative (-) Bus
±200V DC
Distribution
Panel
Distribution
Panel
Distribution Module/Bay
584001200 List 07
Rear
List 21HA
Distribution Panels
Rear
Positive (+) Bus
Negative (-) Bus
±200V DC
P/N 558103 List 21HA
Interconnect Busbar
(two required)
(M8 studs on
1” [25mm] centers)