MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
U
AUTO EQUALIZE IS
DISABLED
or
TURN OFF POWER SHARE
or
AUTO EQUALIZE FOR ##
x DISCHARGE
Initialization
Menu
Allows you to enable the Auto Test/Equalize
feature and set the Auto Test/Equalize
Multiplier set point, or disable the feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to AUTO EQUALIZE IS
DISABLED (displayed when you scroll
down to "zero x discharge").
When the Power Share feature is enabled, the
system cannot be placed in the Test/Equalize
mode.
Note: Test/Equalize Mode requires Power
Share to be turned off. A message is displayed
if Power Share is on. Turn Power Share off
first then return to this menu.
V
NO TEMPERATURE
COMPENSATION
or
TURN OFF POWER SHARE
or
TEMPERATURE SLOPE
= 0.vvvV/ C/F
Initialization
Menu
Allows you to enable the Battery Charge
Temperature Compensation feature and set
the Battery Charge Temperature
Compensation Slope set point, or disable the
feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to NO TEMPERATURE
COMPENSATION (displayed when
you scroll down to "0V / ~").
Note: This is the voltage slope of the entire
battery string, not individual cells.
Note: The Temperature Compensation feature
requires Power Share to be turned off. A
message is displayed if Power Share is on.
Turn Power Share off first then return to this
menu to enable Temperature Compensation.
W
MAXIMUM COMPENSATION
= vv.vvV
Initialization
Menu
Allows you to change the Maximum Voltage
with Temperature Compensation set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
X
MINIMUM COMPENSATION
= vv.vvV
Initialization
Menu
Allows you to change the Minimum Voltage
with Temperature Compensation set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.