User's Manual

Table Of Contents
Section 5877 User Instructions
Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 2-58 Chapter 2. Navigating the MCA
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
F
PCU CURRENT LIMIT
= aaaaaA
or
PCU CURRENT LIMIT
POWER SHARE
Initialization
Menu
Allows you to change the Current Limit set
point. aaaaaA = System current limit setting,
current limit circuit on all Rectifier Modules are
automatically adjusted to ensure system
current does not exceed this value.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Note: When Power Share is enabled, current
limit is controlled by the Power Share feature.
G
SYSTEM HI VOLTAGE #1
= vv.vvV
Initialization
Menu
Allows you to change the System High Voltage
#1 Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
H
SYSTEM HI VOLTAGE #2
= vv.vvV
Initialization
Menu
Allows you to change the System High Voltage
#2 Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
I
BATTERY ON DISCHARGE
= vv.vvV
Initialization
Menu
Allows you to change the Battery on Discharge
Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
J
VERY LOW VOLTAGE
= vv.vvV
Initialization
Menu
Allows you to change the Very Low Voltage
Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
K
TOTAL LOAD CURRENT
= aaaaaA
Initialization
Menu
Allows you to change the Total Distribution
Load Current Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
L
DISTRIBUTION GROUP A
= aaaaaA
Initialization
Menu
Allows you to change the Distribution Group A
Load Current Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
M
DISTRIBUTION GROUP B
= aaaaaA
Initialization
Menu
Allows you to change the Distribution Group B
Load Current Alarm set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.