MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
313
GO TO CONFIGURE MENU
Relay
Assignment
Menu
Press ENTER to go to this menu.
314
GO BACK TO MENU TREE
BEGINNING
Relay
Assignment
Menu
Press ENTER to go to the beginning of the
MCA Menu Tree.
315
NO TEMPERATURE
COMPENSATION
or
TEMPERATURE SLOPE
= 0.vvvV/ C/F
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATE
CURRENT LIMIT
Configure
Menu
Allows you to enable the Battery Charge
Temperature Compensation feature and set
the Battery Charge Temperature
Compensation Slope set point, or disable the
feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to NO TEMPERATURE
COMPENSATION (displayed when
you scroll down to "0V/ C").
Note: This is the voltage slope of the entire
battery string, not individual cells.
Note: The Temperature Compensation feature
requires Power Share and Alternate Current
Limit to be turned off. A message is displayed
if Power Share or Alternate Current Limit is on.
Turn Power Share or Alternate Current Limit off
first then return to this menu to enable
Temperature Compensation.
316
MAXIMUM COMPENSATION
= vv.vvV
Configure
Menu
Allows you to change the Maximum Voltage
with Temperature Compensation set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
317
MINIMUM COMPENSATION
= vv.vvV
Configure
Menu
Allows you to change the Minimum Voltage
with Temperature Compensation set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
318
NOW DISPLAYING C/F
SET TO C/F?
Configure
Menu
Allows you to change the temperature unit
(degrees F or degrees C).
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
319
IT IS NOW hh:mm:ss
dd-mon-yy
Configure
Menu
Allows you to change the time and time.
1. Refer to "Changing a Value or Setting"