User's Manual

Table Of Contents
Section 5877 User Instructions
Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 2-26 Chapter 2. Navigating the MCA
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
215
TEST/EQUALIZE
= vv.vvV
System
Adjustment
Menu
Allows you to change the Test/Equalize Output
Voltage set point.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
216
POWER SHARE IS OFF
TURN IT ON?
or
POWER SHARE IS ON
TURN IT OFF?
or
ALT. LIMIT IS OFF
TURN IT ON?
or
ALT. LIMIT IS ON
TURN IT OFF?
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATE
CURRENT LIMIT
or
TURN OFF TEMPERATURE
COMPENSATION
System
Adjustment
Menu
Allows you to enable or disable the Power
Share or Alternate Current Limit feature.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
or
The Power Share feature requires
Temperature Compensation and Alternate
Current Limit to be turned off. The Alternate
Current Limit feature requires Temperature
Compensation and Power Share to be turned
off. A message is displayed if Temperature
Compensation, Power Share, or Alternate
Current Limit is on. Turn the feature off first,
then return to this menu to enable Power Share
or Alternate Current Limit.
217
PS INITIAL CAPACITY
LIMIT = ##%
System
Adjustment
Menu
Enter the percentage value of the total capacity
of THIS Power System that will initially feed the
load. This value must be set to ensure that the
current delivered by THIS Power System is
lower than the total load current from the two
DC power systems.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
218
PS VOLTAGE OFFSET
= v.vV
System
Adjustment
Menu
Enter the value that will be added to the float
voltage to ensure THIS Power System will
initially carry the load. This value must be
higher than the sum of the voltage drop in the
cables connecting the two systems in parallel
and the output voltage regulation specific to the
rectifiers of the existing DC power system. If
the sense leads are connected to the same
sensing points as the existing DC power
system, the Voltage Offset should take into
consideration the output voltage regulation
only.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.