MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
125
TOTAL PCU OUTPUT
aaaaaA
or
TOTAL PCU/RECTIFIER
aaaaaA
Measurement
Menu
Total Rectifier Module (PCU) output current.
Press ENTER to view individual Rectifier
Module load currents.
or
Total Rectifier Module and legacy rectifier
output current when LMS1000 Function
Channel #64 reported value is greater than
zero.
Press ENTER to view individual Rectifier
Module load currents and legacy system
current.
126
PCU B#-ID#/N#
aaaaaA
PCU
Load Menu
Rectifier Module (PCU) output current. (B#-
ID#/N# = Bay Number-Rectifier Module MCA
ID# w/in Bay/Number of Rectifier Modules in
System).
Press UP and DOWN ARROWS to view other
Rectifier Modules' load currents.
127
RECTIFIER OUTPUT
aaaaaA
PCU
Load Menu
Legacy Rectifier System output current as
reported by the LMS1000 Function Channel
#64.
128
GO TO MEASUREMENT
MENU
PCU
Load Menu
Press ENTER to go to this menu.
129
GO BACK TO MENU TREE
BEGINNING
PCU
Load Menu
Press ENTER to go to the beginning of the
MCA Menu Tree.
130
TEMPERATURE SENSOR
ttt C/F
Measurement
Menu
Temperature detected by Temperature Sensor,
if installed.
131
GO TO FUNCTION MENU
Measurement
Menu
Press ENTER to go to this menu.
132
GO BACK TO MENU TREE
BEGINNING
Measurement
Menu
Press ENTER to go to the beginning of the
MCA Menu Tree.
133
FLOAT MODE IS ACTIVE
SET TEST/EQ?
or
TEST/EQ MODE ACTIVE
SET FLOAT?
or
TEST/EQUALIZE INPUT
IS ACTIVE
or
TURN OFF POWER SHARE
or
TURN OFF ALTERNATE
CURRENT LIMIT
Function
Menu
Allows you to change the Rectifier Module
(PCU) output voltage mode.
1. Refer to "Changing a Value or Setting"
in the table at the beginning of this
chapter.
or
The user tried to set Float Mode while an
external test/equalize input signal was being
supplied to the system.
Note: Test/Equalize Mode requires Power
Share and Alternate Current Limit to be turned
off. A message is displayed if Power Share or
Alternate Current Limit is on. Turn Power
Share or Alternate Current Limit off first then
return to this menu.
134
VIEW THE SYSTEM
INVENTORY
Function
Menu
Press ENTER to go to this menu.