MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
84
RELAY BOARD B#-P# IS
DUPLICATED
Relay Alarm
Detail Menu
Duplicated Reference Designations.
85
RELAY BOARD B#-P#
NO RESPONSE
Relay Alarm
Detail Menu
MCA communications with MCA Customer
Alarm Relay Circuit Card lost. (B#-P# = Bay
Number-Relay Circuit Card Position Number.)
86
GO TO RELAY ALARM
MENU
Relay Alarm
Detail Menu
Press ENTER to go to this menu.
87
GO BACK TO MENU TREE
BEGINNING
Relay Alarm
Detail Menu
Press ENTER to go to the beginning of the
MCA Menu Tree.
88
HIGH TEMPERATURE #1
ALARM
Main
Alarm Menu
Battery ambient temperature above preset
adjustable value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
88A
ALARM LIMIT ttt°C/F
NOW AT ttt°C/F
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
89
HIGH TEMPERATURE #2
ALARM
Main
Alarm Menu
Battery ambient temperature above preset
adjustable value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
89A
ALARM LIMIT ttt°C/F
NOW AT ttt°C/F
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
90
LOW TEMPERATURE #1
ALARM
Main
Alarm Menu
Battery ambient temperature below preset
adjustable value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
90A
ALARM LIMIT ttt°C/F
NOW AT ttt°C/F
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
91
LOW TEMPERATURE #2
ALARM
Main
Alarm Menu
Battery ambient temperature below preset
adjustable value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
91A
ALARM LIMIT ttt°C/F
NOW AT ttt°C/F
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
92
TEMPERATURE SENSOR
NO SIGNAL
Main
Alarm Menu
MCA Temperature Sensor signal lost, if
Temperature Sensor installed.
93
MAJOR MONITORING
ALARM(S)
or
Monitoring Major
LED Messages
Main
Alarm Menu
Major Alarm conditions detected by LMS1000.
Alarm Messages derived from LMS1000 are
displayed by the MCA.
94
MINOR MONITORING
ALARM(S)
or
Monitoring Minor
LED Messages
Main
Alarm Menu
Minor Alarm conditions detected by LMS1000.
Alarm Messages derived from LMS1000 are
displayed by the MCA.