User's Manual

Table Of Contents
Section 5877 User Instructions
Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 2-8 Chapter 2. Navigating the MCA
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
17
GO BACK TO MENU TREE
BEGINNING
PCU
Alarm Menu
Press ENTER to go to the beginning of the
MCA Menu Tree.
18
PCU B#-ID#/N#
EMERG. STOP
PCU Alarm
Detail Menu
Rectifier Module (PCU) is in Emergency Stop
Mode. (B#-ID#/N# = Bay Number-Rectifier
Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
19
PCU B#-ID#/N#
H.V. SHUTDOWN
PCU Alarm
Detail Menu
Rectifier Module (PCU) is in High Voltage
Shutdown. (B#-ID#/N# = Bay Number-Rectifier
Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
20
PCU B#-ID#/N#
AC LINE OFF
PCU Alarm
Detail Menu
No AC Input to Rectifier Module (PCU) or
Rectifier Module's (PCU’s) processor failed.
(B#-ID#/N# = Bay Number-Rectifier Module
MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
21
PCU B#-ID#/N#
AC LINE LOW
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) Low AC Line Alarm
active. (B#-ID#/N# = Bay Number-Rectifier
Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
22
PCU B#-ID#/N#
AC LINE HIGH
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) High AC Line Alarm
active. (B#-ID#/N# = Bay Number-Rectifier
Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
23
PCU B#-ID#/N#
AC PHASE LOST
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) AC Line Phase Lost
Alarm active. (B#-ID#/N# = Bay Number-
Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
24
PCU B#-ID#/N#
POWER FACTOR
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) internal power
factor circuit failed. (B#-ID#/N# = Bay Number-
Rectifier Module MCA ID# w/in Bay/Number of
Rectifier Modules in System.)
25
PCU B#-ID#/N#
DC/DC CONV.
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) internal DC/DC
converter circuit failed. (B#-ID#/N# = Bay
Number-Rectifier Module MCA ID# w/in
Bay/Number of Rectifier Modules in System.)
26
PCU B#-ID#/N#
FUSE/BREAKER
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) DC output fuse
open. (B#-ID#/N# = Bay Number-Rectifier
Module MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
27
PCU B#-ID#/N#
INHIBITED
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) output inhibited.
(B#-ID#/N# = Bay Number-Rectifier Module
MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
28
PCU B#-ID#/N#
ON STANDBY
PCU Alarm
Detail Menu
Rectifier Module's (PCU’s) Standby/Operate
switch is in the "standby" position. (B#-ID#/N#
= Bay Number-Rectifier Module MCA ID# w/in
Bay/Number of Rectifier Modules in System.)