MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
7
1 SYSTEM BREAKER OR
FUSE ALARM
or
### SYSTEM BREAKER &
FUSE ALARMS
Main
Alarm Menu
One or more system fuses or circuit breakers
open. (### = number of open system fuses or
circuit breakers.)
Press ENTER to view which fuse(s) or circuit
breaker(s) is open.
Note that the individual fuses and circuit
breakers in the bullet nose-type device holders
(plug-in) are not counted. If any number within
a bullet nose-type device holder (plug-in) are
open, only one will be counted.
8
F/CB/PI B#-P#A/B
IS OPEN
Fuse
Alarm Menu
Identification of open system fuse or circuit
breaker. (F/CB/PI B#-P#A/B = Fuse or Circuit
Breaker or PlugIn, Bay Number-Distribution
Device Position Number [Group A or B
Designation if applicable.])
Press UP and DOWN ARROWS to scroll if
multiple distribution devices are open.
9
GO TO MAIN ALARM
MENU
Fuse
Alarm Menu
Press ENTER to go to this menu.
10
GO BACK TO MENU TREE
BEGINNING
Fuse
Alarm Menu
Press ENTER to go to the beginning of the
MCA Menu Tree.
11
AC POWER IS OFF TO
ALL PCUs
Main
Alarm Menu
AC input voltage to all Rectifier Modules
(PCUs) below a preset non-adjustable value.
12
1 PCU
HAS FAILED
or
### PCUs
HAVE FAILED
or
NO PCUs ARE
IN INVENTORY
Main
Alarm Menu
One or more Rectifier Modules (PCUs) failed.
(### = number of failed Rectifier Modules
[PCUs].)
Press ENTER to view which Rectifier Module
(PCU) failed.
or
If the MCA does not recognize any Rectifier
Module (PCU), NO PCUs ARE IN INVENTORY
is displayed.
13
PCU B#-ID#/N#
FAILURE
PCU
Alarm Menu
Identification of failed Rectifier Module (PCU).
(B#-ID#/N# = Bay Number-Rectifier Module
MCA ID# w/in Bay/Number of Rectifier
Modules in System.)
Press UP and DOWN ARROWS to scroll if
multiple Rectifier Modules failed.
Press ENTER to view why Rectifier Module
failed.
14
### REMOTE PCUS
HAVE FAILED
PCU
Alarm Menu
More than one Remote Rectifier (PCU) failed.
(### = number of failed Remote Rectifiers
[PCUs].)
15
1 REMOTE PCU
HAS FAILED
PCU
Alarm Menu
One Remote Rectifier (PCU) failed.
16
GO TO MAIN ALARM
MENU
PCU
Alarm Menu
Press ENTER to go to this menu.