User's Manual

Table Of Contents
Section 5877 User Instructions
Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 2-6 Chapter 2. Navigating the MCA
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
3BMCA MESSAGES
The following chart provides an explanation of each MCA message appearing on the
MCA Menu Tree (Section 5886). The MCA Menu Tree is located in the separate
INSTALLATION MANUAL and the CD CARRIER MANUAL (it is also provided on the
CD). Note that each line in the MCA Menu Tree contains a number. This number is
referenced in the following chart.
MCA Menu
Tree Line No.
(Section
5886)
Message Displayed
Associated
with ...
Definition
1
EMERGENCY STOP
INPUT ACTIVE
Main
Alarm Menu
Rectifier Module (PCU) emergency shutdown
or fire alarm disconnect signal applied to the
system.
2
HI VOLTAGE SHUTDOWN
INPUT ACTIVE
Main
Alarm Menu
High voltage shutdown signal applied to the
system.
2A
ALTERNATE CURRENT
LIMIT ACTIVE
Main
Alarm Menu
Indicates that all rectifier modules (PCUs) are
operating in the “Alternate Current Limit” mode.
Rectifier output current will be limited to the
percent of capacity specified by the “Alternate
Current Limit Capacity” parameter setting.
3
SYSTEM VOLTAGE IS
VERY LOW
Main
Alarm Menu
System voltage below a preset adjustable
value, indicating that the battery has been
continuously supplying the load and has
discharged to approximately half its reserve
time.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
3A
ALARM LIMIT vv.vvV
NOW AT vv.vvV
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
4
SYSTEM BATTERY IS ON
DISCHARGE
Main
Alarm Menu
System voltage below a preset adjustable
value, indicating that the battery is supplying
the load and is discharging.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
4A
ALARM LIMIT vv.vvV
NOW AT vv.vvV
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
5
SYSTEM HIGH VOLTAGE
#1 ALARM
Main
Alarm Menu
System voltage above a preset adjustable
value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
5A
ALARM LIMIT vv.vvV
NOW AT vv.vvV
--
Displays the alarm limit setpoint and the actual
value of the monitored input.
6
SYSTEM HIGH VOLTAGE
#2 ALARM
Main
Alarm Menu
System voltage above a preset adjustable
value.
Press ENTER to view the alarm limit setpoint
and the current value of the monitored input.
6A
ALARM LIMIT vv.vvV
NOW AT vv.vvV
--
Displays the alarm limit setpoint and the actual
value of the monitored input.