User's Manual

Table Of Contents
User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 2. Navigating the MCA Page 2-5
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
COMPONENT
MCA IDENTIFICATION NUMBER
MCA NUMBERING
SCHEME (note
that each line
shown below is
separated with a
dash in the MCA
display)
NOTES
EXAMPLE
Distribution
Only Bay’s
Distribution
Bus
Bay #
Distribution Bus #
w/in Bay (A or B
Designation)
Primary Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Distribution Bus #1 = Top Left,
Distribution Bus #2 = Top Right,
Distribution Bus #3 = Bottom Left,
Distribution Bus #4 = Bottom Right,
A or B as set by jumper on MCA Distribution
Bus Monitoring Circuit Card.
Fifth Bay, Top Left
Bus, Set for B
Designation
5-1B
Sixth Bay, Top Right
Bus, Set for B
Designation
6-2B
Seventh Bay, Bottom
Left Bus, Set for B
Designation
7-3B
Seventh Bay, Bottom
Right Bus, Designation
Not Set
7-4
Distribution
Only Bay’s
Distribution
Device
Type
Bay #
Distribution Point #
w/in Bay
Type = Breaker or Fuse or MISC 50-73.
Primary Bay is #1, other bays are numbered
consecutively, following the bay-to-bay cabling
scheme.
Distribution Point =
1-12 (bottom - top, Top Left Bus, Bus #1).
13-24 (top - bottom, Top Right Bus, Bus #2).
25-36 (bottom - top, Bottom Left Bus, Bus #3).
37-48 (top - bottom, Bottom Right Bus, Bus #4).
Note that distribution components may take
more than one mounting position, designation
number is the left most mounting position.
Note: The optional bullet-device fuse panel is
displayed as MISC 50-73.
Fifth Bay, Circuit
Breaker Mounted in
Position One, Bus 1
Set for A Designation
Breaker 5-01A
Sixth Bay, Fuse
Mounted in Position
Thirteen, Bus 2
Designation Not Set
Fuse 6-13