Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 6. System Troubleshooting and Repair Page 6-27
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
REMOVING A BATTERY CHARGE DIGITAL TEMPERATURE
COMPENSATION PROBE FROM A PREVIOUSLY OPERATED
SYSTEM
This procedure details the steps to remove a Battery Charge Digital Temperature
Compensation Probe from a system that has been previously started, configured, and
checked.
Procedure
1) In the Configure Menu, set the SLOPE = 0.vvvV C/F to NO TEMPERATURE
COMPENSATION. Temperature Compensation stops and the System returns to
the FLOAT voltage setting.
2) Remove the probe. The Major Alarm activates. Update inventory to clear this
alarm, as described in this chapter.