User's Manual

Table Of Contents
User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 6. System Troubleshooting and Repair Page 6-13
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Setting
Factory
Default Setting
Required
Site Setting
Float Output Voltage
52.00V
Test/Equalize Output Voltage
52.00V
High Voltage Shutdown
57.50V
Rectifier Current Limit
100% of Rated
Full Load
High Voltage #1 Alarm
55.50V
High Voltage #2 Alarm
56.50V
Battery On Discharge Alarm
51.00V
Very Low Voltage Alarm
47.00V
Total Distribution Load Alarm
2000A
Distribution Group A Load
Alarm
2000A
Distribution Group B Load
Alarm
2000A
High Battery Ambient
Temperature #1 Alarm
Off
High Battery Ambient
Temperature #2 Alarm
Off
Low Battery Ambient
Temperature #1 Alarm
Off
Low Battery Ambient
Temperature #2 Alarm
Off
Digital Temperature
Compensation (Slope)
Off
(0V/ C)
Digital Temperature
Compensation (Maximum
Compensation)
56.50V
Digital Temperature
Compensation (Minimum
Compensation)
50.00V
Table 6-2
MCA Basic Settings