15) Replace fuse F3 which supplies input power to the MCA circuit card. Refer to
Figure 6-7 for location.
16) The MCA goes through an initialization routine (as detailed in Chapter 5.
Installing the Rectifiers and Initially Starting the System of the INSTALLATION
INSTRUCTIONS [Section 5877]). During this initialization routine, check (and if
required change) the MCA settings for your Site. In lieu of manually entering
new MCA settings, if the old MCA configuration was downloaded via the LMS;
upload the configuration. Refer to the LMS User Instructions for a procedure.
17) Remove the grounding wrist strap.
18) Close the bay's front door.
19) Enable the external alarms, or notify appropriate personnel that this procedure is
finished.
20) Ensure that there are no local or remote alarms active on the system.