Page 5-4 Chapter 5. System Maintenance
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
PROCEDURE
REFERENCED IN
VALUE
Measure and Record
System Float
(Output) Voltage
and
Compare MCA
Display Voltage with
Reference Meter
Section 5877, Chapter 2.
Navigating the MCA,
(Line #133) to Place in
Float Mode,
if required.
Record System Output Voltage
as Shown on the MCA Display.
Record also Reference Meter Voltage
Connected to System Output Busbars.
Measure and Record
System Test/Equalize
(Output) Voltage
and
Compare MCA
Display Voltage with
Reference Meter
Section 5877, Chapter 2.
Navigating the MCA,
(Line #133) to Place in
Test/Equalize Mode.
Record System Output Voltage
as Shown on the MCA Display.
Record also Reference Meter Voltage
Connected to System Output Busbars.
Section 5877, Chapter 2.
Navigating the MCA,
(Line #133) to Return to Float Mode.
Measure and Record
Total System Output
Current
Record System Output Current
as Shown on the MCA Display.
Measure and Record
Total Rectifier Output
Current
Section 5877, Chapter 2
Navigating the MCA,
(Line #125).
Note: This table may be reproduced as necessary to record and document system
performance.
Table 5-2 (cont’d on next page)
Procedures that MAY be Performed at 12-Month
Intervals to Track System Operation