User's Manual

Table Of Contents
Section 5877 User Instructions
Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 4-26 Chapter 4. MCA System Adjustments
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
CONFIGURING MCA I/O CIRCUIT CARD BINARY INPUT(S)
1) All controls are located on the MCA Interface Pad.
2) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
3) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"CHANGE CONFIGURATION PARAMETERS" is displayed.
4) Press and release the FUNCTION SET ENTER key.
5) CHANGE I/O BOARD PARAMETERS is displayed. Press and release the
FUNCTION SET ENTER key.
6) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
BINARY INPUT B#-P#-I# IS ALARM = CLOSED or BINARY INPUT B#-P#-I# IS
ALARM = OPEN is displayed (B#-P#-I# = Bay Number MCA I/O Circuit Card
Position Number Binary Input Number).
This setting determines the alarm state of the monitored binary input.
To toggle the setting press and release the ALARM CUTOFF and FUNCTION
SET ENTER keys simultaneously.
“ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
To select another binary input located on the card, press the FUNCTION
SELECT DOWN arrow key. When the last binary input is selected, pressing the
FUNCTION SELECT DOWN arrow key displays the next MCA I/O circuit card
with binary inputs (if available).
7) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Note: If a binary input alarms, the MCA displays a "Binary Input Customer Text
Message" in the I/O Board Alarm Detail Message. If you wish to change
the default message, refer to 'Chapter 3. System Operating Procedures'
for an adjustment procedure.