Chapter 4. MCA System Adjustments Page 4-21
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
CONFIGURING DEGREE UNITS DISPLAYED ( F OR C)
1) All controls are located on the MCA Interface Pad.
2) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
3) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"CHANGE CONFIGURATION PARAMETERS" is displayed.
4) Press and release the FUNCTION SET ENTER key.
5) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"NOW DISPLAYING (C or F) SET TO (F or C)" is displayed.
6) To toggle the degree units being displayed, press and release the ALARM
CUTOFF and FUNCTION SET ENTER keys simultaneously.
7) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
Note: The minimum voltage with temperature compensation value will not be
changed and the adjustment mode will be exited if the FUNCTION SET
YES (+) key is not pressed within 10 seconds of the “ARE YOU SURE?
prompt.
8) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.