MCAALTERNATE CURRENT LIMIT” FEATURE
Description
The MCA Alternate Current Limit feature provides the means to automatically change the
current limit operation of power system’s rectifiers (PCUs) when an external
event/condition occurs.
Operating Modes
Normal Current Limit Operation
When the signal connected to the “Alternate Current Limit Input” is inactive, the system’s
PCUs current limiting feature operates at the value based on the “PCU Current Limit”
parameter setting.
Alternate Current Limit Operation
When the signal connected to the “Alternate Current Limit Input” is active, the system’s
PCUs current limiting feature operates at the value based on the “Alternate Current Limit
Capacity” parameter setting.
Requirements and Conditions
The system must have an MCA I/O circuit card installed.
Binary input #4 must be connected to a signal that will indicate to the MCA to place the
rectifiers into the “Alternate Current Limit” mode.
Programming the MCA Alternate Current Limit Feature
When the Alternate Current Limit is first enabled, the “Alternate Current Limit Capacity”
parameter defaults to a value of 100% of available capacity.
Note: The “Alternate Current Limit” feature is not compatible with the Power Share
feature. If Power Share is programmed ON, then “Turn Off Power Share” is
displayed in the Alternate Current Limit menu.
Note: The PCU current limit menu item setting is ignored when Alternate Current Limit is
enabled AND the Alternate Current Limit Input is active. When this occurs, the
message “ALT. LIMIT” is displayed in the PCU Current Limit menu.
Enabling Alternate Current Limit
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"ADJUST THE SYSTEM VOLTS & AMPS" is displayed.
3) Press and release the FUNCTION SET ENTER key.
4) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"ALT. LIMIT IS OFF, TURN IT ON?" is displayed.
5) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously. "ARE YOU SURE?" is displayed. Press and release the
FUNCTION SET YES (+) key.